American Power Conversion BH500NET, HS 500 user manual Specifications

Models: HS 500 BH500NET

1 4
Download 4 pages 9.38 Kb
Page 3
Image 3
Specifications

8.Following installation, the Back-UPS HS software is available in the Start menu. Upon launching the program, it searches for all Back-UPS HS devices on the network, and will identify them as shown in Figure 8 by IP Address and MAC Address. The IP Address is automatically assigned to the Back-UPS by the DHCP services from your hub or router. IP Addresses assigned by the DHCP service may automatically change over time. Thus, APC recommends you do not bookmark the IP Address, as you may not be able to access it through your browser. The MAC Address is assigned to the Back-UPS HS 500 at the factory.

.

Figure 8. Back-UPS HS IP Address and MAC Address Screen

9.If there are no DHCP services on the network, or if you want to assign an IP Address you can easily remember, you can manually assign an IP Address to the Back-UPS by clicking on the IP Configuration button. The address you assign must follow the format shown in Figure 9 and cannot duplicate an address already assigned. Figure 10 shows the IP Configuration Screen with the IP Address fields set to zero (0).

To assign an IP Address to your computer, please read and follow the directions that came with your computer.

Figure 9. Assign IP Address Screen

Figure 10. Blank Assign IP Address Screen

10.You can assign a name to the Back-UPS by clicking on the Assign Name button (Figure 8) and entering the name in the Assign Name Screen dialog. It will appear in the column to the left of the IP Address of the device (Figure 11). Names should not be duplicated.

Figure 11. Assign Name Screen

11.To reset the Back-UPS HS to factory default values, use the UPS Settings button. If the Back-UPS HS does not reset using the software, remove the Battery Cover and insert a small object (about 2 inches in length) into the hole located next to the telephone jack (Figure 12) for approximately 5 seconds. Note: The telephone jack is provided for factory testing only - do not connect anything to this jack).

Manual background Manual Reset

Access

Figure 12. Manual Reset Access

12.Before performing any UPS maintenance task, check the Status of the UPS by clicking on the Status link. The screen shown in Figure 13 will be displayed.

Figure 13. Back-UPS HS 500 Status Screen

13.To change the configuration of the Back-UPS or perform UPS maintenance, you must log on to the web page (Figure 11) by clicking on the UPS Settings button.

When this page is displayed, enter a default Username of apc, and a default Password of apc. To change the Username or Password, you must log on and then click Maintenance (Figure 14).

Note: You can also access the Logon Page Screen by entering the IP Address into the Address line of your browser.

Figure 14. Log On Screen

14.Using the Maintenance Screen (Figure 15), you can perform a Battery Self- Test, Update the Battery Replacement Date, Change the User Name or Password (as previously discussed) then click Update Now, or you can Restore Factory Defaults. Note: You must be logged on to perform any of these tasks.

Figure 15. Maintenance Page Screen

15.Using the Configuration Page Screen (Figure 14), you can adjust the Sensitivity of the Back-UPS. By adjusting the Sensitivity, the Back-UPS will allow the unit to switch to battery power depending on the quality of the AC utility power being supplied to the unit. Use of the Sensitivity settings are for the following conditions:

Low - Use only for extreme conditions of low input voltage. Not recommended for computer loads.

Medium - Back-UPS frequently goes On Battery due to low input voltage (recommended).

High - Connected equipment is sensitive to low voltage.

The Configuration Page Screen also allows you to enable or disable the Audible Alarm. If enabled, this alarm operates as described in the Status Indicators and Alarms section of this manual. If disabled, the Back-UPS will quiet the alarm.

Additionally, the Configuration Page Screen allows you to adjust the voltage Transfer Points. The Back-UPS will transfer to On Battery operation at input voltages Above or Below the points selected in the drop-down Volts menu.

Finally, the Configuration Page Screen provides Output Control for the four outlets of the Back-UPS. Control consists of switching power On or Off at Output 1, Output 2, or the two outlets of Output 3. It also allows you to Reboot loads by automatically switching power Off and then On at the selected outlet. If an outlet is switched Off, it cannot be rebooted.

To use the Configuration Page Screen, you must be logged on to the Back- UPS. Select the desired function and click on the Apply button. To reset the unit to the factory defaults, click the Reset button.

Figure 16. Configuration Page Screen

16.The About Page Screen provides general information about your Back-UPS including Network Parameters (IP and MAC Addresses), as well as Technical Parameters (Model, Serial Number, Firmware Revision, Web Firmware Revision, UPS Date of Manufacture, and Battery Replacement Date).

Figure 17 About Page Screen

Specifications

Input Voltage (On Line)

95 - 142 Vac

Input Frequency

47 - 63 HZ (autosensing)

 

 

Output Wave Form (On Battery)

Stepped Sine Wave

 

 

 

Maximum Load

500 VA

300 Watts

 

 

 

Operating Temperature

32 - 104° F

(0 to 40° C)

 

 

Storage Temperature

5 - 113° F (-15 to 45° C)

 

 

Operating Humidity

10 - 90% non-condensing

 

 

Storage Humidity

10 - 95% non-condensing

 

 

Physical: (D x W x H)

14.65 x 8.85 x 4.13 in

 

(37.2 x 22.5 x 10.5 cm)

Weight

16.3 lb

(7.4 kg)

 

 

Typical Recharge Time

6 - 8 hours

 

 

EMI Classification

FCC Part 15

 

 

Approvals

cTUVus, FCC Part 15

FCC Part 68, Industry Canada

Page 3
Image 3
American Power Conversion BH500NET, HS 500 user manual Specifications