MX28B-1200+27V PRODUCT MANUAL

 

 

 

 

Input Relay 4 {1}

An alarm activated in response to an external contact closure

In-Rly 4 Alm

m+

[SYSTEM/IN-RLY/RLY-MAP]

or opening at the Input Relay 4 connection.

Ignore

 

 

 

 

 

 

 

 

OUTPUT RELAY SETUP

 

 

 

 

 

 

 

Output Relay 1 Alias {1}

An alternate name (alias) can be assigned to the relay if

Out-Rly 1

m+

[SYSTEM/OUT-RLY/ALIAS]

desired.

Relay 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Relay 6 Alias {1}

An alternate name (alias) can be assigned to the relay if

Out-Rly 6

m+

[SYSTEM/OUT-RLY/ALIAS]

desired.

Relay 6

 

 

 

 

 

 

 

 

Output Relay Minor Alias {1}

An alternate name (alias) can be assigned to the relay if

Relay Minor

m+

[SYSTEM/OUT-RLY/ALIAS]

desired.

Minor

 

 

 

 

 

 

 

 

Output Relay Major Alias {1}

An alternate name (alias) can be assigned to the relay if

Relay Major

m+

[SYSTEM/OUT-RLY/ALIAS]

desired.

Major

 

 

 

 

 

 

 

Output Relay 1 Delay {1}

Delay between sensing of the alarm condition and activation

Out-Rly 1 Dly m+

[SYSTEM/OUT-RLY/RLY-MAP]

of the alarm relay. An alarm condition must exist for longer

0 sec

 

than the delay to be activated.

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Relay 6 Delay {1}

Delay between sensing of the alarm condition and activation

Out-Rly 6 Dly m+

[SYSTEM/OUT-RLY/RLY-MAP]

of the alarm relay. An alarm condition must exist for longer

0 sec

 

than the delay to be activated.

 

 

 

 

 

 

 

Output Relay Alarms

 

 

 

 

 

 

Output Relay 1 {1}

Output Relay 1 alarm can be “mapped” to activate other

Out-Rly 1 Alm m+

[SYSTEM/OUT-RLY/RLY-MAP]

output relays (“Ignore” activates no additional relays).

Ignore

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Relay 6 {1}

Output Relay 6 alarm can be “mapped” to activate other

Out-Rly 6 Alm m+

[SYSTEM/OUT-RLY/RLY-MAP]

output relays (“Ignore” activates no additional relays).

Ignore

 

 

 

 

 

 

 

 

LVD SETUP

 

 

 

 

 

 

 

LVD1 Trip {1}

LVD1 trip (disconnect) threshold voltage.

LVD1 Trip

m+

[MODULES/LVD/PARAM]

 

21.00 V

 

 

 

 

 

 

LVD1 Restore {1}

LVD1 restore (reconnect) threshold voltage.

LVD1 Reset

m+

[MODULES/LVD/PARAM]

 

24.00 V

 

 

 

 

 

 

LVD2 Trip {1}

LVD2 trip (disconnect) threshold voltage.

LVD2 Trip

m+

[MODULES/LVD/PARAM]

 

21.00 V

 

 

 

 

 

 

LVD2 Restore {1}

LVD2 restore (reconnect) threshold voltage.

LVD2 Reset

m+

[MODULES/LVD/PARAM]

 

24.00 V

 

 

 

 

 

 