Install the Switched Rack PDU
Installation guidelines | • If the PDU is installed in an enclosed communications rack, the |
| recommended maximum ambient temperature should be no greater |
| than 45°C. |
| • Install the PDU so that there is air flow to the front and rear face of |
| the unit. |
| • Install the PDU so that there is not an uneven mechanical load. |
| • Follow the nameplate ratings when connecting equipment to the |
| supply circuit. Consider the effect that overloading the circuits |
| might have on |
| • Maintain reliable earthing of the PDU. Give particular |
| consideration to supply connections that do not directly connect to |
| the branch circuit. |
| • The PDU does not provide overcurrent protection. Connect the |
| PDU to an appropriately rated branch circuit. |
| • Install the PDU so that the power plug may be disconnected for |
| service. |
Attach the cord | Attach the cord retention tray to the Switched Rack PDU, using the four |
retention tray |
How to attach cords to the tray
Attach the cord to the tray by looping the cord and securing it to the tray, using a wire tie.
The cord must be secured to the tray so that you can unplug it from the PDU without removing the wire tie.