12 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Low Battery
Warni ng
PowerChute
software interface
provides automatic,
unattended
shutdown when
approximately two
minutes of battery
operated run time
remains.
2 minutes
LED is located
on rear panel
Brightly
illuminated:
low battery warning
level of about 2 minutes
Dimly illuminated:
low battery
warning level of about
5 minutes
No illumination:
low battery warning
level is about 8 minutes
The low-battery warning beeps are continuous
when two minutes of run time remain.
To change the default interval setting, use a
pointed object such as a pen to press the
VOLTAGE SENSITIVIY switch (rear panel),
while
pressing the button, (front display).
Change the low battery warning interval setting
to the time that the operating system or system
software requires to safely shut down.
Synchronized
Turn-on Delay
0 seconds • 0 s
• 60 s
• 120 s
• 180 s
• 240 s
• 300 s
• 360 s
• 420 s
Specify the time the UPS will wait after the
return of utility power before start up, (to avoid
branch circuit overload).
High Transfer Point 208 V models:
225 VAC
120 V models:
127 VAC
230 V models:
253 VAC
• 225 VAC
• 229 VAC
• 127 VAC
• 130 VAC
• 253 VAC
• 257 VAC
• 233 VAC
• 237 VAC
• 133 VAC
• 136 VAC
• 261 VAC
• 265 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically high, set the high
transfer point higher if the connected
equipment can tolerate this condition.
Low Transfer Point 120 V models:
106 VAC
208 V models:
182 VAC
230 V models:
208 VAC
• 97 VAC
• 100 VAC
• 182 VAC
• 178 VAC
• 196 VAC
• 200 VAC
• 103 VAC
• 106 VAC
• 174 VAC
• 170 VAC
• 204 VAC
• 208 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low
transfer point lower if the connected equipment
can tolerate this condition.
Output Voltage
230 V models 230 VAC • 220 VAC
• 230 VAC
• 240 VAC
Set the output voltage of the UPS.
FunctionFactory DefaultUser Selectable Choices Description