Specifications: Required Breaker Settings (400 V Systems)

22 kA is the maximum peak let-through current (including safety factor) available during clearing of an internal fault in a 200 kW section or a Power Module. During or after a controlled fault clearing, none of the breakers are allowed to trip on the instantaneous trip setting below the specified value.

This is also applicable to the upstream breakers, and a control of the instantaneous trip setting in this part of the installation is required. The maximum peak let through current is applicable to utility with prospective short-circuit currents up to 200 kA.

Note

Note

Note

The instantaneous trip setting must not be derated even though the UPS system is derated in system output power. The system size has no influence on the instantaneous trip setting.

For derated or parallel systems, the APC Application Team provides the correct breaker settings and breaker frame sizes.

For upstream breakers not mentioned in the table, the APC Application Team provides the correct breaker settings for on-line, overload, and trip currents.

The diagram shows a dual mains systems in which the upstream breakers are named Q. Correct settings of upstream breaker settings are mandatory. The systems can also be configured as single mains systems.

Dual Mains Single Installation

T1

Q

T2

Q

Q5

Q1

Q3

 

Q6

 

Q2

Q4

32

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D