Installation

Wiring Guidelines

The maximum wiring distance between the Central Controller and the AV2SM is determined by power consumption, supplied voltage, and the wire gauge used for the cable. The maximum wiring lengths for using AXlink power are based on a minimum of 13.5 volts available at the Central Controller’s power supply. The maximum lengths allowable between the AV2SM and the Central Controller are as follows:

Wiring Guidelines

Wiring size Maximum wiring length

181805.7 ft (550.37 m)

201142.4 ft (382.20 m)

22712.2 ft (217.07 m)

24448.9 ft (136.82 m)

Preparing captive wires

1.Strip 0.25 inch of wire insulation off all wires.

2.Insert each wire into the appropriate opening on the connector according to the wiring diagrams and connector types described in this section.

3.Tighten the screws to secure the wire in the connector. Do not tighten the screws excessively; doing so may strip the threads and damage the connector.

Video output connector

Connect your output display monitor to the VIDEO connector on the front panel using FIG. 4.

Video Cable

AV2SM video output connector (female)

BNC connectors (male)

FIG. 4 VIDEO OUTPUT wiring diagram

Output display monitor connector

(female)

 

4

AV2SM A/V Switcher

 

 

 

Page 8
Image 8
AMX AV2SM instruction manual Wiring Guidelines