Options/Accessories

H002a

6.2.5 Switching Back to Normal Parallel/Redundant Operation

1.Turn input switch (Q001) and output switch (Q002) to position “1”

2.Charge capacitor, connect battery and start up UPS

UPS will automatically switch to normal operation and start load-sharing with other parallelled UPS(s).

WARNING!

System will discharge built-in capacitors, but check terminal voltage before proceding.

990-4051

Installation Guide APC Silcon 60-80kW 400V UPS

57

Page 57
Image 57
APC 60-80kW manual Switching Back to Normal Parallel/Redundant Operation