External Connection

UPS

External

External

External PE

Maximum

External

 

Input

Input Cable

Cable

External

Output

 

Fuses* FM

[mm2]

[mm2]

Output

Cable

 

[A]

380-415V

 

Fuses*

[mm2]

 

380-415V

 

 

[A]

 

 

 

 

 

 

 

60kW

125

50

16

100

35

 

 

 

 

 

 

80kW

160

70

35

125

50

 

 

 

 

 

 

NOTICE!

Check correct phase rotation of mains input voltage!!

Max. input/output cables: 120mm2.

If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.

* DIN gL types

UPS

External Alarm

External System

External

External Battery

 

Cable max.

Earth Cable

Battery Breaker

Cable

 

[mm2]

[mm2]**

[A]

[mm2]

 

 

 

 

 

60kW

2

25

125

50

 

 

 

 

 

80kW

2

25

125

50

 

 

 

 

 

NOTICE!

All cable dimensions are recommended sizes only.

Refer to local legal regulations.

PVC cables insulated to withstand ambient temperature of max. 30oC

** Must be rated as external PE cable if mains system is not supplying PE

NOTICE!

Install gland plate in bottom of unit.

 

990-4051

 

 

Installation Guide APC Silcon 60-80kW 400V UPS