Installation

3.0Installation

3.1Requirements on Site

All system parts are accessible from front or top of UPS. Cable entries are accessible from bottom. A 1m free space on all sides should be allowed during installation. Once the system is installed it may be placed close to walls as long as free space is allowed for system doors to open. (Per applicable national and/or local codes.)

For ventilation and service purposes allow for free space of minimum 1m above the unit or per national and/or local codes and in front of UPS. Never install systems in direct sunlight.

NOTICE!

For reliability reasons do not stand on the UPS. keep the UPS cabinet surface free of any objects.

3.1.1 Cabinet Dimensions H*xWxD - 1400xWx800 [mm]. Width as in below table:

* H is 1500 mm for optional IP31 cabinets

 

Width

Width With Built-in Batteries

Width for Separate

 

Without

 

[mm]

 

Battery Cabinets

 

Batteries

 

 

 

[mm]

 

[mm]

 

 

 

 

 

 

 

 

 

 

 

 

UPS

 

1xBP I*

2xBP I*

3xBP I*

1xBP II**

1xBP III***

 

 

 

 

 

 

 

60kW

800

 

 

 

1x800

1x1000

 

 

 

 

 

 

 

80kW

800

 

 

 

1x800

1x1000

 

 

 

 

 

 

 

*BP I = Battery Pack I = 1 x 64 x 7 Ah batteries

**BP II = Battery Pack II = 1 x 64 x 24Ah batteries

***BP III = Battery Pack III = 1 x 64 x 38 Ah batteries

Cabinets

 

 

 

 

 

 

 

 

 

800 mm wide

600 mm wide

 

 

800 mm wide

 

 

 

 

1400 mm

 

 

 

1400 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000 mm wide

1400 mm

60-80kW

APC Isolation

Battery cabinet

Battery cabinet

 

Transformer module

for 1xBP ll

for 1xBP lll

 

10-80kW

 

 

990-4051

 

 

 

 

 

8

Installation Guide APC Silcon 60-80kW 400V UPS

Page 8
Image 8
APC 60-80kW manual Installation, Requirements on Site