8 Installation Guide APC Silcon 60-80kW 400V UPS

990-4051

Installation

3.0 Installation

3.1 Requirements on Site

All system parts are accessible from front or top of UPS. Cable entries are accessible from
bottom. A 1m free space on all sides should be allowed during installation. Once the system is
installed it may be placed close to walls as long as free space is allowed for system doors to open.
(Per applicable national and/or local codes.)
For ventilation and service purposes allow for free space of minimum 1m above the unit or per
national and/or local codes and in front of UPS. Never install systems in direct sunlight.
3.1.1 Cabinet Dimensions H*xWxD - 1400xWx800 [mm]. Width as in below table:
* H is 1500 mm for optional IP31 cabinets
* BP I = Battery Pack I = 1 x 64 x 7 Ah batteries
** BP II = Battery Pack II = 1 x 64 x 24Ah batteries
*** BP III = Battery Pack III = 1 x 64 x 38 Ah batteries
Cabinets
NOTICE!
For reliability reasons do not stand on the UPS. keep the UPS cabinet surface free of any objects.
Width
Without
Batteries
[mm]
Width With Built-in Batteries
[mm]
Width for Separate
Battery Cabinets
[mm]
UPS 1xBP I* 2xBP I* 3xBP I* 1xBP II** 1xBP III***
60kW 800 1x800 1x1000
80kW 800 1x800 1x1000
800 mm wide
60-80kW
1400 mm
APC Isolation
10-80kW
Battery cabinet
for 1xBP ll
1400 mm
1000 mm wide
Battery cabinet
for 1xBP lll
1400 mm
600 mm wide 800 mm wide
Transformer module