APC 7000 Appendix. Check list, Type of UPS, Rectifier, Battery management and protection

Models: 7000

1 15
Download 15 pages 49.24 Kb
Page 13
Image 13

Specification guide

Single UPS, three-phase, 160 to 500 kVA (cont.)

Appendix. Check list

Type of UPS

Total rated power (kVA) at PF 0.9

Manufacturer

Range of products

Operating mode (IEC 62040-2)double conversion Operation as frequency converter

kVA

 

 

kW

yes

 

no

yes

 

 

no

 

 

Rectifier

 

Input voltage range:

250 V to 470 V

3-phase input

without neutral

Phase sequence

Check on phase sequence

Sinusoidal input current

THDI upstream 5% with PFC rectifier

Input power factor

PF > 0.99 with IGBT rectifier

 

(from 50% load)

yes

yes yes yes yes

no no no no no

No inrush or start-up current

Rapid battery recharging

Voltage regulation

Independent regulation/monitoring systems for the charger

Typical 10-min. backup time recharged in six hours or less

± 1%

yes yes

yes yes

no no

no no

Battery

Type standard

other

Service life

Backup time

sealed lead acid in a cabinet

yes

 

 

yes

 

 

 

years

yes

 

 

minutes

yes

 

no no no no

Battery management and protection

Recharge as a function of the temperature

 

yes

Measurement of actual backup time, depending on load, temperature, age

yes

Cold start on battery power

 

yes

Protection against deep discharge

with circuit-breaker opening

yes

Charge-current limiting

0.05 C10 to 0.1 C10 (depending on

yes

 

battery

 

Self-tests

 

yes

Measurement of real backup time

 

yes

Block by block monitoring

 

yes

Prediction on end of service life

 

yes

no no no no no

no no no no

APC by Schneider Electric

Edition - 01/2010

Single UPS spec - p. 13

Page 13
Image 13
APC 7000 dimensions Appendix. Check list, Type of UPS, Rectifier, Battery management and protection