Specification guide

Single UPS, three-phase, 160 to 500 kVA (cont.)

All power and control electronics shall be accessible from the front of the UPS.

2.6. Battery maintenance

For safe maintenance on the battery, the system shall include a circuit breaker to isolate the battery from the rectifier, the charger and the inverter. When the battery is isolated from the system, the UPS shall continue to supply the load without interruption or disturbance, except in the event of a normal AC source outage.

2.7. Cold start (normal AC source absent)

The battery shall be capable of starting the UPS if the normal AC source is absent and continue supplying power to the load within the specified backup time. Cold start on battery power shall be possible on the condition that the system shall have started at least once on normal AC power.

3. Sizing and general characteristics

3.1. Technology

UPS technology shall be based on IGBT transistors for all the power converters (rectifier, charger and inverter with variable chopping frequency).

3.2. Rating

The UPS shall be sized to continuously supply a load of…[160/200250 / 300 / 400 / 500] kVA at a power factor of 0.9.

3.3. Battery backup time

The battery backup time in the event of a normal AC source outage shall be _______ minutes, for a load power

factor of 0.9.

The battery shall be designed for a service life of …[ 10 / 12 ]…years. It shall be selected and sized correspondingly, for a load power factor of 0.9.

3.4. Types of loads accepted

The UPS shall accept high crest factors (3:1) without derating (kW) to ensure correct operation with computer loads and loads where the leading power factor can reach 0.9.

The total harmonic voltage distortion at UPS output (THDU downstream) shall respect the following limits:

ωTHDU downstream ph/ph 3% for non-linear loads.

3.5. PFC sinusoidal-current input rectifier

The UPS system shall not draw a level of harmonic currents that could disturb the upstream AC system, i.e. it shall comply with the stipulations of guide IEC 61000-3-4.

The PFC input rectifier using sinusoidal-current IGBTs shall have the following performance levels:

ωTotal harmonic current distortion (THDI) upstream of the rectifier not exceeding 5%,

ωInput power factor (PF) greater than 0.99 from 50% load upwards.

3.6. Output without a transformer

To reduce losses, dimensions and weight, the UPS output shall be of the transformerless type and the neutral shall be recreated electronically.

3.7. Efficiency

Overall efficiency (between the rectifier input and the UPS output) shall be greater than or equal to:

ω94.5% from 50% load to full rated load (In).

3.8. Noise level

The noise level, measured as per standard ISO3746, shall be less than …[75 dBA (for160, 200, 250, 300, 400, 500 kVA)]

APC by Schneider Electric

Edition - 01/2010

Single UPS spec - p. 3

Page 3
Image 3
APC 7000 dimensions Sizing and general characteristics

7000 specifications

The APC 7000, a renowned product from APC by Schneider Electric, represents a significant advancement in the realm of power conditioning and management. This high-performance uninterruptible power supply (UPS) is engineered to provide reliable and comprehensive protection for critical equipment in various environments, from small businesses to large enterprises.

One of the main features of the APC 7000 is its robust power management capabilities. With an impressive output capacity, this UPS ensures that devices remain powered during outages or fluctuations in voltage. The incorporation of Advanced Battery Management technology maximizes battery life and efficiency, providing users with longer operational time during power disturbances.

The APC 7000 also boasts a user-friendly LCD display, which provides real-time information on the UPS status, including power usage, battery health, and load levels. This intuitive interface allows users to monitor performance at a glance and facilitates easy navigation through the system settings.

In addition to its monitoring capabilities, the APC 7000 integrates SmartSlot technology. This feature enables users to customize the UPS with additional management cards, enhancing its functionality. Users can choose from various options such as network management cards, which allow remote monitoring and control, or environmental monitoring cards that track temperature and humidity levels.

Built with scalability in mind, the APC 7000 supports external battery packs, allowing for increased runtime. This is particularly vital for businesses with extended operational needs during outages. The system also includes intelligent cooling and a heat-sensitive fan, which adjusts its operation based on the load and temperature, thus optimizing performance while reducing noise levels.

Furthermore, the APC 7000 is equipped with multiple output options, including programmable outlets. This feature enables users to manage power distribution efficiently, ensuring essential devices remain operational while less critical equipment can be powered down to conserve battery life.

With its blend of cutting-edge technologies and robust features, the APC 7000 stands out as a reliable powerhouse that meets the demands of modern power protection. Its commitment to performance, user-centric design, and scalability make it an indispensable asset for organizations looking to maintain uptime and safeguard their critical operations. By providing exceptional efficiency and reliable service, the APC 7000 solidifies its position as a leading choice among UPS solutions in today's dynamic technology landscape.