Specification guide

Single UPS, three-phase, 160 to 500 kVA (cont.)

6.5. Safety

For the safety of maintenance personnel, the cabinet shall be provided with a manually operated mechanical bypass designed to isolate the rectifier, charger, inverter and static switch while continuing to supply the load from the bypass AC source.

The UPS shall be equipped with a terminal block for reception of an external EPO order resulting in opening of the battery circuit breaker and shutdown of all converters.

7. Environment conditions

7.1. UPS (not including battery)

7.1.1. Operation

The UPS, not including the battery, shall be capable of operating under the following environmental conditions without loss of performance:

ωTemperature range during continuous operation: 0°C to 35°C

ωMaximum temperature: 40°C for eight hours

ωRecommended temperature range: + 20°C to + 25°C

ωMaximum relative humidity: 95% at 25°C

ωMaximum altitude without derating: 1000 m.

7.1.2. Storage

The UPS, not including the battery, shall be designed for storage under the following conditions:

ωAmbient temperature range: - 10°C to + 45°C.

8.Protection

8.1. UPS

The UPS shall include protection against AC-source over voltages (as per standard IEC 60146), excessive external or internal temperature rise and vibrations and impacts during transport.

8.2. Rectifier and charger

The rectifier shall automatically shutdown if the temperature exceeds the limits specified in section 7.1.1.

The charger shall automatically shut down if the DC voltage reaches the maximum value specified by the battery manufacturer or if the temperature exceeds the limits specified in section 7.1.1.

8.3. Inverter

Inverters shall self-protect against overloads and short-circuits, irrespective of the operating mode (AC power or battery power).

8.4. Battery

8.4.1. Protection against deep discharge and self-discharge

The UPS shall comprise a device designed to protect the battery against deep discharges, taking into account the characteristics of the discharge cycles, with isolation of the battery by a circuit breaker.

8.4.2. Independent regulation and monitoring systems

A regulation system shall regulate the battery voltage and the charge current.

A second system, independent of the regulation, shall monitor the battery voltage and the charge current. Consequently, if the regulation system fails, the monitoring system steps in to shut down the charger and avoid overcharging.

8.4.3.Regulation of the battery voltage depending on the ambient temperature

A temperature sensor adapts the charge voltage to the ambient temperature.

This regulation system takes into account the chemical reaction and prolongs the battery service life. The permissible temperature range is set in the personalization parameters.

An alarm shall be issued for temperatures outside the permissible range.

APC by Schneider Electric

Edition - 01/2010

Single UPS spec - p. 7

Page 7
Image 7
APC 7000 dimensions Environment conditions, Protection, Safety, UPS not including battery, Ups

7000 specifications

The APC 7000, a renowned product from APC by Schneider Electric, represents a significant advancement in the realm of power conditioning and management. This high-performance uninterruptible power supply (UPS) is engineered to provide reliable and comprehensive protection for critical equipment in various environments, from small businesses to large enterprises.

One of the main features of the APC 7000 is its robust power management capabilities. With an impressive output capacity, this UPS ensures that devices remain powered during outages or fluctuations in voltage. The incorporation of Advanced Battery Management technology maximizes battery life and efficiency, providing users with longer operational time during power disturbances.

The APC 7000 also boasts a user-friendly LCD display, which provides real-time information on the UPS status, including power usage, battery health, and load levels. This intuitive interface allows users to monitor performance at a glance and facilitates easy navigation through the system settings.

In addition to its monitoring capabilities, the APC 7000 integrates SmartSlot technology. This feature enables users to customize the UPS with additional management cards, enhancing its functionality. Users can choose from various options such as network management cards, which allow remote monitoring and control, or environmental monitoring cards that track temperature and humidity levels.

Built with scalability in mind, the APC 7000 supports external battery packs, allowing for increased runtime. This is particularly vital for businesses with extended operational needs during outages. The system also includes intelligent cooling and a heat-sensitive fan, which adjusts its operation based on the load and temperature, thus optimizing performance while reducing noise levels.

Furthermore, the APC 7000 is equipped with multiple output options, including programmable outlets. This feature enables users to manage power distribution efficiently, ensuring essential devices remain operational while less critical equipment can be powered down to conserve battery life.

With its blend of cutting-edge technologies and robust features, the APC 7000 stands out as a reliable powerhouse that meets the demands of modern power protection. Its commitment to performance, user-centric design, and scalability make it an indispensable asset for organizations looking to maintain uptime and safeguard their critical operations. By providing exceptional efficiency and reliable service, the APC 7000 solidifies its position as a leading choice among UPS solutions in today's dynamic technology landscape.