APC 7000 dimensions Inverter, Bypass functions, Efficiency, User interface

Models: 7000

1 15
Download 15 pages 49.24 Kb
Page 14
Image 14

Specification guide

Single UPS, three-phase, 160 to 500 kVA (cont.)

Inverter

Three-phase output voltage

adjustable within limits

Steady-state conditions

Voltage transients

Output voltage distortion at Pn

Unbalanced conditions

Output frequency

Variation in output frequency

adjustable from

Frequency synchronization with an external source

Overload capacity

Current limiting

 

Volts

yes

± 3%

 

yes

± 1%

 

yes

± 5% (load from 0 to 100% or 100 to 0%)

yes

THDU < 3%

yes

Voltage variation < 1%

yes

 

Hz

yes

 

± 0.5 Hz

yes

- 0.25 Hz to + 2 Hz

yes

± 0.5% to ± 8% of rated frequency

yes

125% In for 10 minutes

yes

150% In for 30 seconds

yes

230% to 290% In for 150 milliseconds

yes

(e.g. 290% for 160 kVA and 200% for 300

 

kVA)

 

no no no no no no no no no no

no no no

Crest factor

up to 3:1

yes

no

Bypass functions

Automatic bypass

Short-circuit withstand of static switch

With static switch

16 to 25 In for 20 ms, depending on rating

(e.g. 25 In for 250 kVA / 16 In for 500 kVA)

yes

yes

no no

Built-in manual bypass

Mechanical (for maintenance)

yes

no

Efficiency

 

 

 

Normal mode

93 % (160 kVA) to > 94.5% from 75%

yes

 

 

 

load

 

 

no

User interface

Graphical display

selection of operating language from 19

personalization menu

with password

display

measurements, status, events, graphs

event log

2500 time-stamped events

bar graphs

power levels, backup time

statistics

% time on battery power, number of

 

transfers to battery power, average

 

percent load, etc.

Controls

ON, OFF, EPO terminal block

Status indications with mimic panel

Audio alarm, LEDs

yes

yes

yes

yes

yes

yes

yes

yes

no no no no no no

no no

APC by Schneider Electric

Edition - 01/2010

Single UPS spec - p. 14

Page 14
Image 14