Chapter 2 Monitoring the System

Monitoring a UPS

Step 5 Verify that the Cisco ICS 7750 can communicate with the UPS:

fmmcli getchassisinfo more

Information similar to the following will be displayed:

UPS status = AC

Battery Level = <non-zero value>

Batt. Span = <non-zero value>

Note If UPS status = UpsNotAvailable is displayed, verify that your system components are properly connected and powered on. Then try this procedure again.

Step 6 Unplug the UPS power cord.

The UPS emits an audio tone, and the ALARM LED on the SAP turns on (amber).

Step 7 Using the Telnet session that you opened at Step 2, enter the following command to verify that the system has detected the change in power status:

fmmcli getchassisinfo more

Information similar to the following will be displayed:

UPS status = DC

Battery Level = <non-zero value>

Batt. Span = <non-zero value>

Step 8 Open an ICS System Manager session (see “Accessing ICS System Manager” on page 1-9).

Step 9 Click the Event Manager tab on the ICS System Manager home page. Step 10 At the bottom of the Live Viewer page, click Start Events.

Information similar to the following will be displayed:

AC power is off, using DC

 

 

Cisco ICS 7750 Administration and Troubleshooting Guide

 

 

 

 

 

 

78-10169-02 Rev. B0

 

 

2-27

 

 

 