6.0 UPS Monitoring

6.4 Computer interface port

The computer interface port is diagramed below for your reference. Those with technical abilities wishing to use this port in a special application should be aware of the following limitations and capabilities of the interface.

Outputs at pins 3, 5 and 6 are actually open collector outputs which must be pulled up to a common referenced supply no greater than +40 Vdc. The transistors are capable of a maximum non-inductive load of 25 mAdc. Use only Pin 4 as the common.

The output at Pin 2 will generate a LO to HI RS-232 level upon transfer of the output load to power derived from the UPS’s battery. The pin is normally at a LO RS-232 level.

The UPS will shut down when a HI RS-232 level, sustained for 4.5 s, is applied to Pin

1. The UPS responds to this signal, following a delay, only during mains failures (load is operating from the UPS’s internal power source).

An unregulated +24 Vdc appears at Pin 8 of the interface port whenever the UPS is powered. The supply is limited to 40 mAdc maximum.