9.0 Specifications

Note: Where specifications ratings differ, values for the 220/230/240 Vac versions are given in [ ] brackets.

9.1 Input

Nominal input voltage: single phase, 120 Vac, [220/230/240 Vac].

Nominal input frequency: 50 or 60 Hz, internally selected by microprocessor.

Input protection; 600VA, 900VA model: 14 Amp, [12 Amp] resettable circuit breaker.

Input protection, 2000VA model: [15 Amp] resettable circuit breaker.

9.2 Transfer characteristics

Frequency limits for on-line operation: 50 or 60 Hz, ±5%.

Lower input voltage limit for on-line operation: 90 Vac, [173 Vac; when set for operation at the nominal 240 Vac line, the lower input voltage limit is increased to 180 Vac]. Upper input voltage limit for on-line operation: 132 Vac, [253 Vac; when set for operation at the nominal 240 Vac line, the upper input voltage limit is increased to 264 Vac].

SmartBoost operation input voltage range: 90 to 103 Vac, [173 to 196 Vac; when set for operation at the nominal 240 Vac line, the SmartBoost input voltage range is increased to 180 to 204 Vac].

Transfer time: 2 ms typical, 4 ms maximum. Note that 1 ms is 0.001 seconds.

9.3 Output characteristics

Maximum load, 600VA model: 600 VA or 400 W @ 0.67 power factor.

Maximum load, 900VA model: 900 VA or 630 W @ 0.7 power factor.

Maximum load, 2000VA model - 120 Vac version: 2000 VA or 1500 W @ 0.75 power factor with supplied NEMA L5-30P installed; 1000 VAor 1000 W with supplied NEMA 5-15P installed; 1500VAor 1500 W as supplied. See section3.0 for maximum load ratings of models with wiring device options.

Maximum load, 2000VA model - 220/230/240 Vac versions: 2000 VA or 1500 W @ 0.75 power factor.

On-battery output voltage: 115 Vac, [225 Vac] ±5%. The 220/230/240 Vac version may be set to provide a nominal 240 Vac, see section 5.0.

On-battery frequency: 50 or 60 Hz, ±0.1 Hz unless synchronized to mains frequency during utility brownout.

On-battery waveshape: low distortion sinewave.

Protection: overcurrent and short circuit protected, latching shutdown upon overload.