APC 990-2258B-001 Specifications, AC input, AC output, Battery input,   

Models: 990-2258B-001

1 6
Download 6 pages 43.73 Kb
Page 4
Image 4


Network Management card

SpecificationsAC inputAC outputBattery inputManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Remove the two screws from the cable-inlet at the front and remove the cable- inlet plate.

Guide the cable through the hole in the bottom plate and up through the cable- inlet.

Guide the cable through the side panel hole and run the cable upwards inside the panel.

Pull the cable out of the side panel through the hole closest to the Network Management Card area.

Plug the cable into the probe socket / PowerChute inlet.

Specifications

Warning: The UPS must be supplied from a 380/220 V, 400/230 V or 415/240 V L1, L2, L3, N, PE, 50 Hz.

AC input

 

 

10 kVA

 

UPS ratings

380 V

400 V

415 V

 

 

 

 

Input frequency (Hz)

40-70

40-70

40-70

Nominal input current (A)1

13.0

12.3

11.9

Max. input current (A)2

14.3

13.5

13.1

Input current limit (A)3

16.8

16.8

16.8

 

15 kVA

20 kVA

UPS ratings

380 V 400 V 415 V

380 V 400 V 415 V

 

 

 

AC output

 

 

 

 

 

10 kVA

 

UPS ratings

 

 

 

380 V

400 V

415 V

 

 

 

 

 

 

 

Nominal output current (A)

 

 

 

15.2

14.4

13.9

 

 

 

 

 

 

 

 

 

15 kVA

 

 

20 kVA

 

UPS ratings

380 V

400 V

415 V

380 V

400 V

415 V

 

 

 

 

 

 

Nominal output current (A) 22.8

21.7

20.9

30.4

28.9

27.8

 

 

 

 

 

 

 

 

 

30 kVA

 

 

40 kVA

 

UPS ratings

380 V

400 V

415 V

380 V

400 V

415 V

 

 

 

 

 

 

Nominal output current (A) 45.6

43.3

41.7

60.8

57.7

55.6

 

 

 

 

 

 

 

Manual backgroundManual backgroundManual backgroundManual backgroundManual background

Manual background

Reattach the cable-inlet plate ().

Input frequency (Hz)

40-70

40-70

40-70

40-70

40-70

40-70

Nominal input current (A)1 19.4

18.5

17.8

26.0

24.7

23.8

Max. input current (A)2

21.4

20.3

19.6

28.6

27.2

26.2

Input current limit (A)3

25.2

25.2

25.2

33.8

33.8

33.8

 

 

30 kVA

 

 

40 kVA

 

UPS ratings

380 V

400 V

415 V

380 V

400 V

415 V

 

 

 

 

 

 

 

Input frequency (Hz)

40-70

40-70

40-70

40-70

40-70

40-70

Nominal input current (A)1

38.6

36.7

35.3

51.7

49.1

47.3

Max. input current (A)2

42.5

40.3

38.9

56.8

54.0

52.1

Input current limit (A)3

50.1

50.1

50.1

66.9

66.9

66.9

 

 

 

 

 

 

 

Battery input

UPS ratings

10 kVA

15 kVA

20 kVA

30 kVA

40 kVA

 

 

 

 

 

 

Nominal voltage (V)

± 192

± 192

± 192

± 192

± 192

External battery fuse (A)

125

125

125

125

125

 

1.6-1.75 V/cell (automatic, depending on load)

 

 

 

 

 

 

4

Page 4
Image 4
APC 990-2258B-001 important safety instructions Specifications, AC input, AC output, Battery input,   