Specifications
Warning: The UPS must be supplied from a 380/220 V, 400/230 V or 415/240 V L1, L2, L3, N, PE, 50 Hz.
AC input
|
| 10 kVA |
|
UPS ratings | 380 V | 400 V | 415 V |
|
|
|
|
Input frequency (Hz) | |||
Nominal input current (A)1 | 13.0 | 12.3 | 11.9 |
Max. input current (A)2 | 14.3 | 13.5 | 13.1 |
Input current limit (A)3 | 16.8 | 16.8 | 16.8 |
| 15 kVA | 20 kVA |
UPS ratings | 380 V 400 V 415 V | 380 V 400 V 415 V |
|
|
|
AC output
|
|
|
|
| 10 kVA |
|
UPS ratings |
|
|
| 380 V | 400 V | 415 V |
|
|
|
|
|
|
|
Nominal output current (A) |
|
|
| 15.2 | 14.4 | 13.9 |
|
|
|
|
|
|
|
|
| 15 kVA |
|
| 20 kVA |
|
UPS ratings | 380 V | 400 V | 415 V | 380 V | 400 V | 415 V |
|
|
|
|
|
| |
Nominal output current (A) 22.8 | 21.7 | 20.9 | 30.4 | 28.9 | 27.8 | |
|
|
|
|
|
|
|
|
| 30 kVA |
|
| 40 kVA |
|
UPS ratings | 380 V | 400 V | 415 V | 380 V | 400 V | 415 V |
|
|
|
|
|
| |
Nominal output current (A) 45.6 | 43.3 | 41.7 | 60.8 | 57.7 | 55.6 | |
|
|
|
|
|
|
|
Reattach the cable-inlet plate ().
Input frequency (Hz) | ||||||
Nominal input current (A)1 19.4 | 18.5 | 17.8 | 26.0 | 24.7 | 23.8 | |
Max. input current (A)2 | 21.4 | 20.3 | 19.6 | 28.6 | 27.2 | 26.2 |
Input current limit (A)3 | 25.2 | 25.2 | 25.2 | 33.8 | 33.8 | 33.8 |
|
| 30 kVA |
|
| 40 kVA |
|
UPS ratings | 380 V | 400 V | 415 V | 380 V | 400 V | 415 V |
|
|
|
|
|
|
|
Input frequency (Hz) | ||||||
Nominal input current (A)1 | 38.6 | 36.7 | 35.3 | 51.7 | 49.1 | 47.3 |
Max. input current (A)2 | 42.5 | 40.3 | 38.9 | 56.8 | 54.0 | 52.1 |
Input current limit (A)3 | 50.1 | 50.1 | 50.1 | 66.9 | 66.9 | 66.9 |
|
|
|
|
|
|
|
Battery input
UPS ratings | 10 kVA | 15 kVA | 20 kVA | 30 kVA | 40 kVA |
|
|
|
|
|
|
Nominal voltage (V) | ± 192 | ± 192 | ± 192 | ± 192 | ± 192 |
External battery fuse (A) | 125 | 125 | 125 | 125 | 125 |
| |||||
|
|
|
|
|
|