EPO wiring – pin connections J108. Connect the EPO cable using

one of the following four wiring configurations.

XR battery enclosure

Front panel removal.

Use a coin or similar to

J108

EPO circuit

J108

+24 V

EPO circuit 0V

J108

EPO circuit

J108

+24 V

EPO circuit 0 V

1: Dry Contacts Normally Open

EPO is activated when pin 1 is connected to pins 3 and 5.

Connections: 2-4-6,

3-5 and 1 ( )

2: +24 V Normally Open

EPO is activated when an isolated SELV 24 VDC voltage is supplied on pin 1 with reference to pin 2.

Connections: 3-5 and 4-6.

3: Dry Contacts Normally Closed

EPO is activated when a connection from pin 3 to pin 5 is opened.

Connections: 4-6.

4: +24 V Normally Closed

EPO is activated when a SELV 24 VDC voltage is removed from pin 3 with reference to pin 4.

J200

BAT

BAT

Note: When connecting the Q3 auxiliary signal, use gold- plated N/C auxiliary switch.

Note: Reinstall the cable landing cover.

Connect APC communication options

Note: The cable routing of the power chute software and the temperature sensor is identical.

Note: The temperature sensor is provided in a plastic bag attached to the front of the UPS behind the front panel.

turn the two black lock

devices on either side of the

display in the direction of

each other to a vertical

positon.

Push the front panel upwards and pull it outwards to disengage the locking device at the top of the enclosure.

Lift the front panel free of the two slots at the bottom of the enclosure.

Pin connections J106 (UPS).

J106

Charging control switch

Q3 switch

J200 (XR

Batteries)

Pins 1 to 4 are for battery measurement (only applicable to MGE Galaxy 3500 XR Battery Enclosures (see J200 drawing).

Pins 5 and 6 are for external maintenance bypass Q3 (auxiliary switch N/C type).

When Q3 is closed, signals are fed back to the UPS controller (see Q3 drawing).

Pins 7 and 8 are for external charge control. When 7 and 8 are closed, the UPS charges batteries with a pre-defined percentage (0-25-50-75-100%) of the maximum charging power. To be used in generator applications, or if special codes require control of charging.

When Q3 is closed, signals are fed back to the UPS controller.

3

Page 3
Image 3
APC 990-2258B-001 important safety instructions Connect APC communication options