Overview
Front panel
- OK
- Warning
- Overload
B1 |
| B2 | - OK |
TOTA L | - Warning | ||
|
| - Overload | |
|
|
|
Link - Rx/Tx 10/100
Status
Input | A | Output | Preference |
| |||
| B | ||
| B | A | |
|
|
|
Amps
Reset
Press to select data
Automatic
Transfer Switch
Serial Port
pdu0392a
| Item | Description |
|
|
|
| Source A and B LEDs | Provide information about the input voltage from each source. |
|
| If the RMS input voltage and the measured frequency are |
|
| within the selected tolerance range, the corresponding indicator |
|
| will light. |
|
| In a normal operating condition (full source redundancy), both |
|
| LEDs are illuminated. |
|
|
|
| Connector LEDs | Indicate which source is being used for the output (only one |
|
| arrow will be lit at any time). The combination of Source |
|
| LEDs, Connector LEDs, and Output LED provide a graphical |
|
| view of the power flow through the ATS. |
|
|
|
| Output LED | Shows that voltage is available at the output for the ATS. |
|
|
|
| Preference key | Sets the preferred source to supply power to the load |
|
| equipment. In normal operation, if both sources are available, |
|
| the ATS will use the preferred source. Press the Preference key |
|
| to change the preferred source. Press and hold for ten seconds |
|
| to restart the ATS. The restart occurs without resetting |
|
| communications and is confirmed when both status LEDs flash |
|
| off, then on. |
|
|
|
| Preference A and B | Indicate which of the two sources is selected as the preferred |
| LEDs | source. If both LEDs are off, neither source is selected. If the |
|
| sources are asynchronous, the LED for the selected source will |
|
| flash once per second. |
|
|
|
| Reset switch | Restarts ATS network and serial communication. |
|
|
|
| Digital display | Digital display of the current used by the ATS and attached |
|
| devices: |
|
| • Shows the aggregate current for the bank/phase |
|
| corresponding to the Bank/Phase Indicator LED that is |
|
| illuminated. |
|
| • Cycles through the banks/phases in |
|
|
|
| Control key | • Press to change the bank/phase of the current displayed on the |
|
| digital display. |
|
| • Press and hold for five seconds to display the IP address of the |
|
| ATS. |
|
|
|
Automatic Transfer | 3 |