Web

Path: Administration > Network > Web > options

Option

Description

 

 

access

To activate changes to any of these selections, log off from the Rack PDU:

 

Disable: Disables access to the Web interface. (To re-enable access, log in to the command line

 

interface, then type the command http -S enable. For HTTPS access, type https -S

 

enable.)

 

Enable HTTP (the default): Enables Hypertext Transfer Protocol (HTTP), which provides

 

Web access by user name and password, but does not encrypt user names, passwords, and data

 

during transmission.

 

Enable HTTPS: Enables Hypertext Transfer Protocol (HTTPS) over Secure Sockets Layer

 

(SSL). SSL encrypts user names, passwords, and data during transmission, and authenticates the

 

Rack PDU by digital certificate. When HTTPS is enabled, your browser displays a small lock

 

icon.

 

See “Creating and Installing Digital Certificates” in the Security Handbook, available at

 

www.apc.com.

 

HTTP Port: The TCP/IP port (80 by default) used to communicate by HTTP with the Rack

 

PDU.

 

HTTPS Port: The TCP/IP port (443 by default) used to communicate by HTTPS with the Rack

 

PDU.

 

For either of these ports, you can change the port setting to any unused port from 5000 to 32768

 

for additional security. Users must then use a colon (:) in the address field of the browser to specify

 

the port number. For example, for a port number of 5000 and an IP address of 152.214.12.114:

 

http://152.214.12.114:5000

 

https://152.214.12.114:5000

ssl

Add, replace, or remove a security certificate.

certificate

Status:

 

 

Not installed: A certificate is not installed, or was installed by FTP or SCP to an incorrect

 

location. Using Add or Replace Certificate File installs the certificate to the correct location,

 

/ssl on the Rack PDU.

 

Generating: The Rack PDU is generating a certificate because no valid certificate was found.

 

Loading: A certificate is being activated on the Rack PDU.

 

Valid certificate: A valid certificate was installed or was generated by the Rack PDU. Click on

 

this link to view the contents of the certificate.

 

If you install an invalid certificate, or if no certificate is loaded when you enable

 

SSL, the Rack PDU generates a default certificate, a process which delays access to

 

the interface for up to one minute. You can use the default certificate for basic encryption-

 

based security, but a security alert message displays whenever you log on.

 

Add or Replace Certificate File: Enter or browse to the certificate file created with the

 

Security Wizard.

 

See “Creating and Installing Digital Certificates” in the Security Handbook, available at

 

www.apc.com, to choose a method for using digital certificates created by the Security Wizard or

 

generated by the Rack PDU.

 

Remove: Delete the current certificate.

 

 

63

Metered Rack PDU User Guide

Page 71
Image 71
APC AP8861, AP8886, AP88XX manual Web, Option Description, Status

AP8886, AP88XX, AP8861 specifications

The APC AP8861, part of the AP88XX series, is a highly versatile and advanced power distribution unit (PDU) designed to meet the growing demands of data centers and IT environments. This series encompasses state-of-the-art technologies and features designed to enhance both operational efficiency and reliability.

The AP8861 model is particularly recognized for its modular design, allowing for easy scaling and expansion as data center needs evolve. With a variety of outlet configurations, it can accommodate numerous devices while optimizing power management. The device supports both standard and high-density power distribution, making it suitable for diverse environments, from small server rooms to large-scale data centers.

One of the hallmark features of the AP8861 is its built-in network management capabilities. It allows for real-time monitoring of power consumption, ensuring optimal load balancing and helping prevent overload situations. The device incorporates environmental monitoring through temperature and humidity sensors, enabling administrators to proactively manage operating conditions and mitigate risks to sensitive equipment.

The AP88XX series features advanced Surge Protection, which guards against electrical surges that can damage connected equipment. This is a critical consideration in data centers where the integrity of sensitive electronics is paramount. Additionally, the series supports remote management, allowing IT personnel to monitor and control power distribution from anywhere in the world. This function enhances operational flexibility and facilitates rapid responses to power-related issues.

Another significant characteristic of the AP8861 is its compatibility with APC's software solutions. Integrating seamlessly with IT management platforms enables deeper insights and analytics, leading to informed decision-making regarding power usage and equipment reliability.

The device boasts a high-efficiency design, contributing to reducing overall energy costs. The capability to customize alarm settings for power events and environmental factors further enhances proactive management of the data center environment.

In summary, the APC AP8861 and the entire AP88XX series are engineered for robust performance, enhanced control, and adaptability in power distribution management. Packed with advanced features, this series offers solutions that help businesses optimize their data centers while ensuring maximum uptime and equipment protection, thereby supporting the ever-increasing demands placed on modern IT infrastructures.