Console

Path: Administration > Network > Console > options

Option

Description

 

 

access

Choose one of the following for access by Telnet or Secure SHell (SSH):

 

Disable: Disables all access to the command line interface.

 

Enable Telnet (the default): Telnet transmits user names, passwords, and data without

 

encryption.

 

Enable SSH: SSH transmits user names, passwords, and data in encrypted form, providing

 

protection from attempts to intercept, forge, or alter data during transmission.

Configure the ports to be used by these protocols:

Telnet Port: The Telnet port used to communicate with the Rack PDU (23 by default). You can change the port setting to any unused port from 5000 to 32768 for additional security. Users must then use a colon (:) or a space, as required by your Telnet client program, to specify the non- default port. For example, for port 5000 and an IP address of 152.214.12.114, your Telnet client requires one of the these commands:

telnet 152.214.12.114:5000 telnet 152.214.12.114 5000

 

SSH Port: The SSH port used to communicate with the Rack PDU (22 by default). You can

 

change the port setting to any unused port from 5000 to 32768 for additional security. See the

 

documentation for your SSH client for the command line format required to specify a non-default

 

port.

 

 

ssh host

Status indicates the status of the host key (private key):

key

SSH Disabled: No host key in use: When disabled, SSH cannot use a host key.

 

Generating: The Rack PDU is creating a host key because no valid host key was found.

 

Loading: A host key is being activated on the Rack PDU.

 

Valid: One of the following valid host keys is in the /ssh directory (the required location on the

 

Rack PDU):

 

•A 1024-bit or 2048-bit host key created by the Security Wizard

 

•A 2048-bit RSA host key generated by the Rack PDU

 

Add or Replace: Browse to and upload a host key file created by the Security Wizard.

 

To use the APC Security Wizard, see the Security Handbook, available at www.apc.com.

 

Note:To reduce the time required to enable SSH, create and upload a host key in advance. If you

 

enable SSH with no host key loaded, the Rack PDU takes up to one minute to create a

 

host key, and the SSH server is not accessible during that time.

 

Remove: Remove the current host key.

Note: To use SSH, you must have an SSH client installed. Most Linux and other UNIX platforms include an SSH client, but Microsoft Windows operating systems do not. Clients are available from various vendors.

Metered Rack PDU User Guide

64

Page 72
Image 72
APC AP8886, AP88XX, AP8861 manual Console, Telnet 152.214.12.1145000 telnet 152.214.12.114

AP8886, AP88XX, AP8861 specifications

The APC AP8861, part of the AP88XX series, is a highly versatile and advanced power distribution unit (PDU) designed to meet the growing demands of data centers and IT environments. This series encompasses state-of-the-art technologies and features designed to enhance both operational efficiency and reliability.

The AP8861 model is particularly recognized for its modular design, allowing for easy scaling and expansion as data center needs evolve. With a variety of outlet configurations, it can accommodate numerous devices while optimizing power management. The device supports both standard and high-density power distribution, making it suitable for diverse environments, from small server rooms to large-scale data centers.

One of the hallmark features of the AP8861 is its built-in network management capabilities. It allows for real-time monitoring of power consumption, ensuring optimal load balancing and helping prevent overload situations. The device incorporates environmental monitoring through temperature and humidity sensors, enabling administrators to proactively manage operating conditions and mitigate risks to sensitive equipment.

The AP88XX series features advanced Surge Protection, which guards against electrical surges that can damage connected equipment. This is a critical consideration in data centers where the integrity of sensitive electronics is paramount. Additionally, the series supports remote management, allowing IT personnel to monitor and control power distribution from anywhere in the world. This function enhances operational flexibility and facilitates rapid responses to power-related issues.

Another significant characteristic of the AP8861 is its compatibility with APC's software solutions. Integrating seamlessly with IT management platforms enables deeper insights and analytics, leading to informed decision-making regarding power usage and equipment reliability.

The device boasts a high-efficiency design, contributing to reducing overall energy costs. The capability to customize alarm settings for power events and environmental factors further enhances proactive management of the data center environment.

In summary, the APC AP8861 and the entire AP88XX series are engineered for robust performance, enhanced control, and adaptability in power distribution management. Packed with advanced features, this series offers solutions that help businesses optimize their data centers while ensuring maximum uptime and equipment protection, thereby supporting the ever-increasing demands placed on modern IT infrastructures.