150/175kw Modular PDU Installation8
Bottom entry installation
Note: The sidecar is required for undefloor wiring into the PDU. The Sidecar does not contain a switch
or circuit breaker so a readily accessible disconnect device shall be incorporated external to the
equipment.
1Remove the dedicated cover plate. Drill holes
in the plate for conduits and re-install the
plate with the conduits installed. Route the
conductors (input conductors in single utility
systems or bypass conductors in dual utility
systems) through the bottom of the Side Car.
2Connect the input/bypass conductors to the
L1, L2, L3, EGC, and GEC terminals and
torque to specifications on label.
Sidecar Model PDU Model
PDPM150SC PDPM150G6F
PDPM150L6F
PDPM100SC PDPM175G6H