7150/175kw Modular PDU Installation
Install Input Power Cables

Top entry installation

1Open the front door. Unlatch and swing the display
interface and bracket out towards the front door.
2Loosen the captive screws and remove the top
safety panel.
3Loosen the captive screws and remove the front top
plate.
4Remove the dedicated cover plate.
Drill holes in the plate for conduits
and re-install the plate with the
conduits installed.
5Connect the input power cables.
For PDPM150L6F:
L1, L2, L3 - Torque: 28.3 Nm
(250 lb-in).
Ground - Torque: 5.6 Nm (50 lb-in).
For PDPM150G6F and
PDPM175G6H:
L1, L2, L3 - Torque: 31.1 Nm
(275 lb-in).
Ground - Torque: 5.6 Nm (50 lb-in).
6Grounding Electrode Conductor -
Torque: 62.2 Nm (550 lb-in).
pdx0830a
1
2
3

Input Power

pdx0847a

L1L2 L3

4
5
5
6