APC SMX48RMBP2U, SMX750 VA, SMX 1500 VA Using the controllable outlet groups and UPS outlets

Models: SMX1000 VA SMX 1500 VA SMX750 VA SMX48RMBP2U

1 21
Download 21 pages 5.91 Kb
Page 12
Image 12

Using the controllable outlet groups and UPS outlets

The UPS outlets function as a master switch. They turn on first when power is applied, shut off last when there is a power outage and battery runtime has been exhausted.

The UPS outlets must be turned on for the Controllable Outlet Groups to turn on.

1.Connect critical equipment to the UPS outlets (The 1500 VA units do not have UPS outlets. Connect all critical equipment to the same outlet group.)

2.Connect peripheral equipment to the Controllable Outlet Groups.

Nonessential equipment that should shut off quickly in the event of a power outage to conserve battery runtime can be added to a short power off delay

If equipment has dependent peripherals that must restart or shut down in a specific order, such as an ethernet switch that must restart before a connected server, connect the devices to separate groups

Equipment that needs to reboot independently from other equipment should be added to a separate group

3.Use the Configuration menus to configure how the Controllable Outlet Groups will react in the event of a power outage.

10

Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U

Page 12
Image 12
APC SMX48RMBP2U, SMX750 VA, SMX 1500 VA, SMX1000 VA operation manual Using the controllable outlet groups and UPS outlets