Use one of the following cable types to connect the Symmetra RM to the EPO switch:
CL2 | Class 2 cable for general use. |
CL2P | Plenum cable for use in ducts, plenums, and other spaces used for environmental air. |
CL2R | Riser cable for use in a vertical run in a shaft of from floor to floor. |
CL2X | Limited use cable for use in dwellings and for use in raceway. |
For installation in Canada: Use only CSA Certified, type ELC
Connection Option 1
An electrician must connect 1 to 2. Then, both 3 and 4 must be connected to a normally open (NO) switch contact.
| 200 Ohms | PTC | 1 |
|
|
| 2 |
+120 V | 24 Vdc |
| |
VMID | circuit breaker |
| |
trip coil | 3 | ||
|
|
| |
|
|
| 4 |
| 200 Ohms | PTC |
|
Figure 5: EPO Connection Option 1
Connection Option 2
An electrician must connect the 12 Vdc source and a normally open (NO) switch contact to 2 and 3.
| 200 Ohms | PTC | 1 |
|
|
| 2 |
+120 V | 24 Vdc |
| |
VMID | circuit breaker |
| |
trip coil | 3 | ||
| 200 Ohms | PTC | 4 |
Figure 6: EPO Connection Option 2
Install Modules Into the Symmetra RM Frame
• |
|
Œ Ž |
|
Œ | • |
| |
Œ | • |
| |
Œ | • |
|
Œ= Power Module
•= Redundant Intelligence Module Ž = Main Intelligence Module
•= Battery Module
Figure 7: Bay Identification
The intelligence modules are shipped in the Symmetra RM frame. After the frame is installed in the rack you must install the power and battery modules into the frame.
15