Install battery modules just prior to running the Symmetra RM. The battery modules discharge slowly when loaded prematurely and can be damaged permanently.

Each battery module weighs 21.8 kg (48 lbs). Two people are required to install or remove battery modules.

Battery Module: With one person on either side of the battery module, lift the module, and slide it completely into the frame to engage the internal electrical connector. The top of each battery module has a tab to align the module connector with the connector inside the bay. This tab ensures that only battery modules will fit into the bay.

Tighten the two (2) screws to secure the module.

Position battery modules in the bays on the right before filling bays on the left.

Power Module: Lift the power module, and slide the module into a bay until flush with frame to engage the internal connector. The side of the power module has a lever Œ to help align the connector on the module with the connector inside the bay. It also locks the power module in place.

Tighten the two (2) screws to secure the module.

Œ

Œ

Install cover plates, included with the unit, over any unused bays.

Connect Equipment to the Symmetra RM

Power is distributed to the connected equipment via the power distribution panel (PDU) on the rear panel of the Symmetra RM. Labeling on the rear panel indicates the circuit breaker/outlet groups.

220/230/240 (L1-N-G) PDU Panel

200/208 (L1-L2-G) PDU Panel

Eight (8) x IEC-320-C13

Two (2) L6-20

Two (2) IEC-320-C19

One (1) L6-30

Figure 8: Power Distribution Panels

Use your equipment’s power cord to connect to the UPS.

Turn on all connected equipment (the equipment will not be powered until the Symmetra RM is turned on).

Add accessories for the accessories slot. See the literature accompanying the accessory for details.

This UPS is equipped with an accessory slot. See the APC website (apcc.com) for available accessories.

If a standard accessory is installed on this UPS, follow the installation instructions included with the accessory.

16

Page 20
Image 20
APC SYBT2, SYPM2KU, 990-1031 Connect Equipment to the Symmetra RM, 220/230/240 L1-N-G PDU Panel 200/208 L1-L2-G PDU Panel