Aprilaire 1770A, 1750A VENTILATION oR Air Cycling, Whole-Homewith Ventilation, Ventilation Wiring

Models: 1770A 1750A

1 20
Download 20 pages 61.23 Kb
Page 12
Image 12
VENTILATION oR Air Cycling

VENTILATION oR Air Cycling

The dehumidifier has outputs available to open a normally closed damper and introduce outdoor air though an outdoor air intake duct.. Ventilation is controlled by the Cycle Period switches, Cycle Time potentiometer, and Vent-Auto/Vent-Timed switches.. If a normally closed ventilation damper is not installed, the dehumidifier will function in Air Cycling mode, activating the HVAC blower to cycle air through the home based on the Cycle Period and Cycle Time..

DUCTING & WIRING

Required Components

Aprilaire Model 6506, 6” Normally Closed Damper

24 VAC Transformer (10VA min..) for Ventilation Damper

Optional Component

8052 Outdoor Temperature Sensor

Figure 19 – Whole-Home with Ventilation

Figure 20 – Ventilation Wiring

DEHUMIDIFIED AIR IS SUPPLIED

DOWNSTREAM FROM A-COIL TO

MINIMIZE EVAPORATION OFF A-COIL

SUPPLY DUCT

HVAC / FURNACE

115 VAC CIRCUIT

FLOOR DRAINFigure 19 – Whole-Home with VentilationFigure 20 – Ventilation WiringDETERMINE VENTILATION REQUIREMENTS DEHUMIDIFIER

A-COIL

RETURN

DUCT NORMALLY CLOSED VENT DAMPER

AIR IS PULLED FROM

RETURN DUCT

6" NORMALLY

24 VAC

CLOSED DAMPER

(10 VA min)

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUNCTIONS IN

THERMOSTAT

HVAC EQUIPMENT

AIR CYCLING

 

 

MODE IF

R

R

DAMPER NOT

C

C

INSTALLED

G

 

 

 

 

 

G

 

W

W

 

Y

Y

OPTIONAL OUTDOOR

DEHUMIDIFIER

CONTROL BOARD

T VEN DEH Rf Cf Gs Gh W DH FLOAT ODT

DAMPERS P EQUIHVACRSWITCH SENSO

CONDENSATE HOSE

(TO COMMON DRAIN OR OUTSIDE)

Ducting Note: Direct ducting the ventilation intake duct to the dehumidifier inlet duct is acceptable if the incoming temperature of the mixed air will be greater than 40°F and less than 100°F.

TEMPERATURE SENSOR

See page 14 for outdoor temperature sensor installation.

A B + - REMOTE

90-1536

90-1537

DETERMINE VENTILATION REQUIREMENTS

CALCULATING AIRFLOW REQUIREMENT

 

 

 

 

 

 

 

 

 

 

 

 

 

1. The MINIMUM ventilation requirement is calculated using

 

 

 

 

 

 

Table 3 – CFM Required

 

 

 

 

ASHRAE 62..2-2007..

 

 

 

 

 

 

 

 

 

 

 

 

Number of Bedrooms

 

ASHRAE Airflow in CFM = [House Area in Sq.. Ft.. x 0..01]

House Sq. Ft.

 

 

 

 

 

 

 

+ [(Number of Bedrooms +1) x 7..5]

 

2

3

4

5

6

Notes: Use ‘Number of Bedrooms +1’ or the ‘Number of

 

 

 

 

 

 

1000

35

40

50

 

 

Occupants’, whichever is larger..

 

 

 

 

 

 

1500

40

45

55

60

70

2. Table 3 shows calculated airflow values to the nearest 5 CFM..

 

 

 

 

 

 

2000

45

50

60

65

75

If more outdoor air is required, a second device is advised..

3. Record the Required CFM.. __________

 

 

 

 

 

 

2500

50

55

65

70

80

 

 

 

 

 

 

 

 

3000

55

60

70

75

85

 

 

 

 

 

 

 

 

3500

 

 

75

80

90

 

 

 

 

 

 

 

12

Page 12
Image 12
Aprilaire 1770A, 1750A VENTILATION oR Air Cycling, Whole-Homewith Ventilation, Ventilation Wiring, Ducting & Wiring