VENTILATION oR Air Cycling
The dehumidifier has outputs available to open a normally closed damper and introduce outdoor air though an outdoor air intake duct.. Ventilation is controlled by the Cycle Period switches, Cycle Time potentiometer, and
DUCTING & WIRING
Required Components
Aprilaire Model 6506, 6” Normally Closed Damper
24 VAC Transformer (10VA min..) for Ventilation Damper
Optional Component
8052 Outdoor Temperature Sensor
Figure 19 – Whole-Home with Ventilation
Figure 20 – Ventilation Wiring
DEHUMIDIFIED AIR IS SUPPLIED
DOWNSTREAM FROM
MINIMIZE EVAPORATION OFF
SUPPLY DUCT
HVAC / FURNACE
115 VAC CIRCUIT
FLOOR DRAIN DEHUMIDIFIER
RETURN
DUCT NORMALLY CLOSED VENT DAMPER
AIR IS PULLED FROM
RETURN DUCT
6" NORMALLY | 24 VAC | ||||||
CLOSED DAMPER | |||||||
(10 VA min) | |||||||
|
|
|
|
| TRANSFORMER | ||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
FUNCTIONS IN | THERMOSTAT | HVAC EQUIPMENT | |
AIR CYCLING | |||
|
| ||
MODE IF | R | R | |
DAMPER NOT | C | C | |
INSTALLED | G |
| |
|
| ||
|
| G | |
| W | W | |
| Y | Y |
OPTIONAL OUTDOOR
DEHUMIDIFIER
CONTROL BOARD
T VEN DEH Rf Cf Gs Gh W DH FLOAT ODT
DAMPERS P EQUIHVACRSWITCH SENSO
CONDENSATE HOSE
(TO COMMON DRAIN OR OUTSIDE)
Ducting Note: Direct ducting the ventilation intake duct to the dehumidifier inlet duct is acceptable if the incoming temperature of the mixed air will be greater than 40°F and less than 100°F.
TEMPERATURE SENSOR
See page 14 for outdoor temperature sensor installation.
A B + - REMOTE
DETERMINE VENTILATION REQUIREMENTS
CALCULATING AIRFLOW REQUIREMENT |
|
|
|
|
|
| |
|
|
|
|
|
|
| |
1. The MINIMUM ventilation requirement is calculated using |
|
|
|
|
|
| |
Table 3 – CFM Required |
|
|
|
| |||
ASHRAE |
|
|
|
| |||
|
|
|
|
|
| ||
|
| Number of Bedrooms |
| ||||
ASHRAE Airflow in CFM = [House Area in Sq.. Ft.. x 0..01] | House Sq. Ft. |
|
| ||||
|
|
|
|
| |||
+ [(Number of Bedrooms +1) x 7..5] |
| 2 | 3 | 4 | 5 | 6 | |
Notes: Use ‘Number of Bedrooms +1’ or the ‘Number of |
|
|
|
|
|
| |
1000 | 35 | 40 | 50 |
|
| ||
Occupants’, whichever is larger.. |
|
|
|
|
|
| |
1500 | 40 | 45 | 55 | 60 | 70 | ||
2. Table 3 shows calculated airflow values to the nearest 5 CFM.. | |||||||
|
|
|
|
|
| ||
2000 | 45 | 50 | 60 | 65 | 75 | ||
If more outdoor air is required, a second device is advised.. | |||||||
3. Record the Required CFM.. __________ |
|
|
|
|
|
| |
2500 | 50 | 55 | 65 | 70 | 80 | ||
|
|
|
|
|
|
| |
| 3000 | 55 | 60 | 70 | 75 | 85 | |
|
|
|
|
|
|
| |
| 3500 |
|
| 75 | 80 | 90 | |
|
|
|
|
|
|
|