Aprilaire 1750A, 1770A SPOT installation continued, Ducting & Wiring, Spot Ducted Installation

Models: 1770A 1750A

1 20
Download 20 pages 61.23 Kb
Page 9
Image 9
SPOT installation (continued)

SPOT installation (continued)

DUCTING & WIRING

Figure 14 – Spot Ducted Installation

 

RETURN DUCT

OUTSIDE AIR TO HOUSE

 

 

DEHUMIDIFIED AIR

 

 

SUPPLY DUCT

 

IS SUPPLIED

 

TO DUCTED SPACE

 

 

 

 

LIVING SPACE

 

115 VAC

 

HVAC FURNACE

CIRCUIT

 

 

 

GRILLE WITH

 

 

8" DUCT COLLAR

EQUIPMENT ROOM

 

AIR IS PULLED

 

 

CONDENSATE HOSE

DEHUMIDIFIER

FROM AREA

(TO COMMON DRAIN

 

 

 

OR OUTSIDE)

FLOOR DRAIN

 

 

 

 

 

90-1536

Wiring Notes:

No additional wiring required.

If wiring to a Model 70 Living Space Control, see

MODEL 70 LIVING SPACE CONTROL section on page 16..

If wiring to a third-party control, see THIRD-PARTY

CONTROL section on page 17..

DIP SWITCH CONFIGURATION

CYCLE PERIOD: This determines how frequently the dehumidifier will sample the air to check the humidity level.. Set to 1 hour and adjust as needed..

For Ventilation switch settings, see VENTILATION section beginning on page 12.

For Local/External switch setting, see THIRD-PARTY CONTROL on page 17.

Figure 15 – Spot DIP Switch Settings

SYSTEM SETUP

LOCAL

1

 

 

 

ON

EXTERNAL

 

 

 

HVAC FAN OFF

2

 

 

 

HVAC FAN ON

 

 

 

 

WHL HOUSE

3

 

 

 

 

CONVERTIBLE

VENT-AUTO

4

 

 

 

 

VENT-TIMED

CYCLE PERIOD

1

 

 

 

 

 

ON

30 MIN.

 

 

 

 

 

2

 

 

 

 

 

1 HOUR

 

 

 

 

 

 

3

 

 

 

 

 

 

2 HOUR

4

 

 

 

 

 

 

3 HOUR

 

 

 

 

 

 

 

 

90-1538

SEQUENCE OF OPERATION

Sampling will occur at the end of the Cycle Period. At the onset of sampling, the dehumidifier damper output turns on, the dehumidifier blower turns on, and the green Status LED flashes..

After three minutes, the dew point of the incoming air is measured and compared to the set point on the control knob. If the dew point of the incoming air is above the set point, the compressor turns on and the green Status LED switches to solid illumination.. If the dew point is below the set point, the dehumidifier damper output turns off and the dehumidifier blower turns off along with the green Status LED.. The next sampling will occur at the end of the next Cycle Period..

The dew point of the incoming air is continuously monitored during compressor operation. When the dew point of the incoming air falls below the set point on the control knob, the dehumidifier damper output turns off and the dehumidifier compressor and blower turn off along with the green Status LED..

9

Page 9
Image 9
Aprilaire 1750A, 1770A SPOT installation continued, Ducting & Wiring, Spot Ducted Installation, Wiring Notes, System Setup