Specifications
Dimensions:
Adjustable feet allow for
Weight: 1750A – 93 lbs.. 1770A – 100 lbs..
Capacity: 1750A – 90 pints per day @ 275 CFM 1770A – 135 pints per day @ 500 CFM AHAM
Power: 1750A – 115 VAC, 8 A, 15 A circuit 1770A – 115 VAC, 14 A, 20 A circuit
Unit equipped with 8 ft.. grounded power cord
Operating Conditions:
Compressor:
Ambient/Inlet Air:
Filter: MERV 8, washable
Compressor Minimum Off Time: 3 minutes
Compressor Minimum On Time: 3 minutes
Airflow:
1750A
External Static Pressure | Airflow |
|
|
0..0 “w..c.. | 385 CFM |
|
|
0..4 “w..c.. | 340 CFM |
|
|
0..6 “w..c.. | 275 CFM |
|
|
|
|
1770A |
|
|
|
External Static Pressure | Airflow |
|
|
0..0 “w..c.. | 535 CFM |
|
|
0..7 “w..c.. | 515 CFM |
|
|
0..9 “w..c.. | 500 CFM |
|
|
UNPACKING AND CONTENTS
Do not tip unit to remove from carton.
1.Open carton completely by cutting each corner from top to bottom..
2.Remove all cardboard inner pack..
3.See Figure 1 for opening view and contents..
a..Installation Instructions
b..Owner’s Manual
c..Duct Collars, 2
d..Drain Trap
e..90° PVC Elbow
f..Backflow Damper
Figure 1 – Opening View and Contents | |||
|
| b | a |
|
|
| |
| c |
|
|
f |
| d |
|
| e |
| |
|
|
| |
|
|
|
3