DIP SWITCH CONFIGURATION
•HVAC FAN ON: Activating the HVAC fan during dehumidification is recommended because it offers better circulation and balancing of indoor air conditions.. Running the HVAC fan during dehumidification does not affect moisture removal efficiency.. If the switch is put in the HVAC FAN OFF position, air is pulled through the unit, dehumidified, and circulated solely by the dehumidifier blower..
•CYCLE PERIOD: This determines how frequently the dehumidifier will sample the air to check the humidity level.. Set to 1 hour and adjust as needed..
•For Ventilation switch settings, see VENTILATION section beginning on page 12.
•For Local/External switch setting, see
Figure 13 – Whole-Home DIP Switch Settings
SYSTEM SETUP
LOCAL | 1 |
| ON | EXTERNAL |
| ||||
HVAC FAN OFF | 2 |
| HVAC FAN ON | |
|
| |||
WHL HOUSE | 3 |
|
| CONVERTIBLE |
4 |
|
|
CYCLE PERIOD
1 |
|
| ON | 30 MIN. |
|
| |||
2 |
|
| 1 HOUR | |
|
|
| ||
3 |
|
|
| 2 HOUR |
4 |
|
|
| 3 HOUR |
|
|
|
|
|
SEQUENCE OF OPERATION
•Sampling will occur once within the Cycle Period. Sampling is initiated with the first HVAC fan (Gs) call or at the end of the Cycle Period if a HVAC fan call is not received within the Cycle Period.. At the onset of sampling, the dehumidifier damper output turns on, the dehumidifier blower turns on, and the green Status LED flashes..
•After three minutes, the dew point of the incoming air is measured and compared to the set point on the control knob. If the dew point of the incoming air is above the set point, the compressor turns on and the green Status LED switches to solid illumination.. If the dew point is below the set point, the dehumidifier damper output turns off and the dehumidifier blower turns off along with the green Status LED..
•The dew point of the incoming air is continuously monitored during compressor operation. When the dew point of the incoming air falls below the set point on the control knob, the dehumidifier damper output turns off and the dehumidifier compressor and blower turn off along with the green Status LED..
SPOT installation
In this installation the dehumidifier is not ducted to the HVAC system and is used to dehumidify a specific area.. This installation is typically used in basements or crawl spaces.. The dehumidifier can remain
Required Components
Duct Work
Grilles with 8” duct collars
Optional Components
Condensate Pan & Normally Closed Float Switch
Model 70 Living Space Control