Aprilaire 60 & 62 installation instructions Humidifier operates constantly

Models: 60 & 62

1 15
Download 15 pages 17.7 Kb
Page 14
Image 14

SYMPTOM

Humidifier operates constantly.

If the humidity level in the home is less than the Humidifier Control knob setting and there is a continuous fan call or heat call (depending on setup), the Humidifier Control will operate the humidifieruntil the humidity level is higher than the Humidifier Control knob setting.

TROUBLESHOOTING PROCEDURE

Set Blower Activation switch to OFF.

In the “Test/Reset” mode, verify that the humidifier turns off after 1 minute.

Check the Outdoor Temperature Sensor resistance and location, as instructed on the previous page.

Rotate the Humidifier Control knob counterclockwise to the “Off” position, and observe whether the humidifier turns off. If the humidifier still operates in the “Off” position, perform the following:

1.Check the wiring diagram for correct Humidifier Control Installation.

2.Remove the wires from the “H” terminals on the Humidifier Control. If the humidifier continues to operate, replace the solenoid valve.

SYMPTOM

Humidifier or Humidifier Control “chatters” or clicks On and Off rapidly.

TROUBLESHOOTING PROCEDURE

Check for steady 22 VAC to 30 VAC across the “R” and “C” terminals of the Humidifier Control with a voltmeter.

Check, with a voltmeter, that the HVAC signal across the “W” and “C” and “G and C” terminals of the Humidifier Control is a steady 22 VAC to 30 VAC.

Make sure that the Outdoor Temperature Sensor wiring is not running alongside other wires carrying high voltage (120 VAC or higher). (Automatic Mode Only)

SYMPTOM

Humidifier blower does not activate during Blower Activation Test.

TROUBLESHOOTING PROCEDURE

Set the Blower Activation Switch to “ON”.

Check wiring diagrams for correct Humidifier Control installation.

26

27

Page 14
Image 14