Part 4 Trouble Shooting

8) Troubleshooting CH32, CH33, CH40

 

 

 

 

 

 

Error

Title

 

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

 

D-pipe (Inverter)

 

• Check the discharge pipe sensor for INV.

 

• Discharge sensor

• Check the install condition for over load.

32

temp. high

 

 

(105°C(221°F)

)

(Inverter) temp. high

• Check the leakage of refrigerant.

 

 

• Check the SVC V/V open.

 

 

 

 

 

 

 

 

 

 

D-pipe (Constant)

 

• Check the discharge pipe sensor for Cons.

 

• Discharge sensor

• Check the install condition for over load.

33

temp. high

 

 

(Cons.) temp. high

• Check the leakage of refrigerant.

 

(105°C(221°F)

)

 

 

• Check the SVC V/V open.

 

 

 

 

 

 

 

 

 

 

 

 

• Open/Short

 

40

CT Sensor

 

• Soldered poorly

 

• Internal circuit error

• Normal resistor : about 0

 

 

 

 

 

 

 

 

 

 

 

D-Pipe temp.

 

 

Toff(105) °C

 

 

(221)

°F

T2(95) °C

 

 

(203)

°C

T1(90) °C

 

 

(194)

°C

COMP Frequency

Normal

Normal

OFF

 

(Hz)

 

 

 

 

 

LEV Openness

Normal

Normal

OFF Control

 

(Pulse)

 

 

 

 

 

Check Point

CH 32

1.Check the install condition for over load.

2.Check the SVC V/V open.

3.Check the leakage of refrigerant.

CH 40

1.If the resistance of the sensor is only , the check Is possible.

2If the error occurs again after the reset , change the PCB.

CH 33

1.Check the install condition for over load.

2.Check the SVC V/V open.

3.Check the leakage of refrigerant.

4.Check the constant compressor. (same with CH21)

Service Manual 63

Page 63
Image 63