LG Electronics General Wall Mounted-Inverter Type Troubleshooting CH21, Copper Comp pipe

Models: General Wall Mounted-Inverter Type

1 67
Download 67 pages 5.96 Kb
Page 58
Image 58

Part 4

Trouble Shooting

 

 

3) Troubleshooting CH21

 

 

 

 

 

 

Error

Title

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

• An instant over current in the U,V,W phase

 

 

• Instant over current

- Comp lock

21

 

- The abnormal connection of U,V,W

DC Peak

• Over Rated current

• Over load condition

 

 

• Poor insulation of IPM

- Overcharging of refrigerant

 

 

 

- Pipe length.

 

 

 

• Poor insulation of compressor

 

 

 

 

 

Comp

 

U

 

V

W

Copper

Comp pipe

Resistance(Ω) at 20°C(68°F)

Terminal

Inverter

Constant

comp.

comp.

 

 

 

 

U-V

0.64

0.8

V-W

0.64

0.8

W-U

0.64

0.8

 

Resistance() at 20°C(68°F)

 

 

 

Terminal

Inverter

Constant

comp.

comp.

 

 

 

 

U-GND

2M

2M

V-GND

2M

2M

W-GND

2M

2M

Check Point

1.Check the wire connection. (U,V,W)

2.Check the load condition. (Refrigerant, Pipe length, …) Adjust the load condition

3.Check the electricity leakage of the compressor. Normal : Over 2M.

4.Check the resistance of compressor. Normal : 0.65(INV), 0.8(Cons.) No difference at each terminal.

5.Check the insulation from water at IPM part. Check the trace of water.

6.Check the IPM circuit.

58Room Air Conditioner