LG Electronics General Wall Mounted-Inverter Type manual Check before Test Run

Models: General Wall Mounted-Inverter Type

1 67
Download 67 pages 5.96 Kb
Page 31
Image 31

Part 3 Test Run

1. Checkbefore Test Run

1

Check to see whether there is any refrigerant leakage, and check whether the power or transmission

cable is connected properly.

 

2

3

Check whether the liquid pipe and gas pipe valves are fully opened.

NOTE: Be sure to tighten caps.

Confirm that 500 V megger shows 2.0 Mor more between power supply terminal block and ground. Do not operate in the case of 2.0 Mor less.

NOTE: Never carry out mega ohm check over terminal control board.

Otherwise the control board may break.

Immediately after mounting the unit or after leaving it turned off for an extended length of time, the resistance of the insulation between the power supply terminal board and the ground maydecrease to approx. 2.0 Mas a result of refrigerant accumulation in the internal compressor.

If the insulation resistance is less than 2.0 M, turn on the main power supply.

Service Manual 31

Page 31
Image 31
LG Electronics General Wall Mounted-Inverter Type manual Check before Test Run