LG Electronics General Wall Mounted-Inverter Type DC Peak control, Discharge Pipe Temp Control

Models: General Wall Mounted-Inverter Type

1 67
Download 67 pages 5.96 Kb
Page 25
Image 25

Part 2 Functions & Controls

5.10 DC Peak control

5.10.1 DC Peak Current Error by a fault signal of IPM

If the operating current of IPM reaches 35A 3A, the compressor stops instantly.

If DC PEAK occurs 5 times within 1 hour, the appliance turns off and displays Error Code 6(9,12kBtu/h Model) / Error Code 21(18,24,30kBtu/h Model).

5.10.2 DC Peak Current Error by the compressor lock

If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the appliance turns off and display Error Code 6(9k,12k Model) / Error Code 23(18k,24k,30k Model).

5.10.3 DC Peak Current Error by the Outdoor Fan Lock

If this problem occurs 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C(149°F) while the compressor is operating, the appliance turns off and displays Error Code 6(9,12kBtu/h Model) / Error Code 61(18,24,30kBtu/h Model).

5.11 Discharge Pipe Temp Control

5.11.1 9,12kBtu/h Model

If the temperature of the discharge pipe of compressor reaches over 130°C(266°F) or below -30°C(-22°F) the com- pressor stops instantly.

The compressor operating frequency is limited according to the compressor dome TH. (Refer to below Fig.)

Temperature range of COMP SPEC varies by 10°C(50°F).

 

D-Pipe Temp.

 

 

T = (T off - T2)/2

T off °C

 

 

 

 

T1 = T2

- 2 * T

 

 

 

 

 

T3 = T2

+ T

 

T3 °C

 

 

 

 

 

 

 

T2 °C

 

 

 

 

 

 

 

T1 °C

 

 

 

 

 

 

 

-13 °C(8.6°CF)

 

 

 

 

 

 

 

COMP Freq. Fh min

Free

Fc-1

Fc-2

OFF

Fc-2

Fc-1

Free

T off : 110°C(230°F) ( Model by model )

T2 : 100°C(212°F) ( Model by model )

NOTE: Some Models are different by T1, and T2.

Service Manual 25

Page 25
Image 25
LG Electronics General Wall Mounted-Inverter Type manual DC Peak control, Discharge Pipe Temp Control