SYSTEM START-UP
The Energy Recovery Ventilator has an on/off switch which enables the unit to be constantly on.. There is also wiring access and wire leads available in the unit for connection to the Aprilaire Home Comfort Control™, Aprilaire Model 8120 Ventilation Controller, or any
Constant On Operation
1.Plug in the power cord to a 120VAC grounded outlet..
2.Turn on/off switch on..
Operation With Home Comfort Control™ (Figure 20)
1.Remove the front panel of the ERV..
2.Remove the wire nut from the two yellow wires..
3.Run
4.Insert the wire through the ERV wire access port..
5.Use wire nuts to connect each end of the
6.Replace the ERV front panel..
7.Connect the other end of the
8.Reference the Home Comfort Control™ Installation Instructions to set the ventilation timing per the
9.Plug in the ERV..
10.Turn the on/off switch ON..
Operation With 8120 Ventilation Controller or
1.Remove the front panel of the ERV..
2.Remove the wire nut from the two yellow wires..
3.Run
4.Insert the wire through the ERV wire access port..
5.Use wire nuts to connect each end of the
6.Replace the ERV front panel..
7.Connect the other end of the
8.Use the tables below to determine the airflow requirement and cycle time to meet the
a.Table. 2 on the following page shows the required ventilation rate in CFM..
b.Table. 3 on the following page shows the required ventilation cycle time in minutes based on a 1 hour cycle using the airflow determined in Table 1..
9.Plug in the ERV..
10.Turn the on/off switch ON..
Figure 20 – Wiring to External Control | APRILAIRE MODEL 8120 | |
| ||
| VENTILATION CONTROLLER | |
| A/A | |
| OR | |
| VENT | |
| VENT | |
| HOME COMFORT CONTROL™ | |
YELLOW WIRES | OR | |
| ||
TRANSFORMER | 24 VAC, DRY CONTACT, | |
NORMALLY OPEN | ||
RELAY | ||
|
10