Aprilaire 8100 manual DUCTING Duct work Specifications, GrillE and Hood Specifications

Models: 8100

1 12
Download 12 pages 35.99 Kb
Page 6
Image 6
DUCTING

MECHANICAL INSTALLATION (continued)

DUCTING

Duct work Specifications

Plan on temporarily installing two air flow measuring devices. The system will have to be balanced (BALANCING THE SYSTEM SECTION), after all duct work has been installed.. The measuring devices are removed after the system has been balanced..

A sound absorber at least 6 ft. long, consisting of 1” thick rigid fiberglass duct or insulated flexible duct is recommended for maximum absorption of air movement sounds between the unit and the living space return grille..

All flexible ducts must meet UL safety standards for Class 1 air ducts and connectors.

All ducting must be installed according to local HVAC codes and standards.

Round 6” galvanized duct or equivalent is recommended for all duct runs that do not require insulation.

All ducting located in an unheated space must be completely sealed and insulated.

For optimum performance and quite operation, all duct runs should be kept as short, straight, and equal in length as possible.

If the ERV will not be running continuously, a field supplied butterfly damper must be installed in the intake duct near the hood.

GrillE and Hood Specifications

The living space return grille should not be less than 75 in2 of free area.. Grille surfaces less than this may produce excess air noise..

Exterior intake and exhaust hoods must be weather resistant. The hoods must also incorporate a screen to prevent unwanted debris, animals, and insects from entering the duct work.. The screen should have a maximum of ¼” openings..

Caulk both hoods to prevent water leakage.

Intake and exhaust hoods should be above the expected snow line or a minimum of 18” above ground level, whichever is greater.

Duct work Connections – ForceD Air System

All duct collars are clearly labeled and must be connected properly.

Rigid duct work should be connected to the collars with sheet metal screws.

Flexible duct work must be connected with clamps or bands.

All duct connections should be sealed with duct tape or mastic to prevent leakage.

Figure 14 – Fully Ducted Energy Recovery Ventilator

NOTE: FRESH AIR INLET TO RETURN DUCT 10 FEET MINIMUM FROM HVAC BLOWER.

GrillE and Hood Specifications FRESH AIR TO HOUSE

Duct work Connections – ForceD Air System STALE AIR TO OUTSIDE

STALE AIR FROM HOUSE

(CENTRALLY LOCATED SUCH AS HALLWAY)

AIR MOVEMENT

SOUND ABSORBER

STALE AIR FROM HOUSE

FRESH AIR FROM OUTSIDE Manual backgroundManual background

BUTTERFLY DAMPER Manual background

(IF ERV NOT RUNNING CONTINUOUSLY)

10 FT MINIMUM

NOTE: THE FRESH AIR INTAKE SHOULD BE INSTALLED

A MINIMUM OF 10 FEET FROM ANY EXHAUST VENT.

90-1747

6

Page 6
Image 6
Aprilaire 8100 DUCTING Duct work Specifications, GrillE and Hood Specifications, Duct work Connections - ForceD Air System