TROUBLESHOOTING – AHC CONNECTION

Symptom

Cause

 

 

 

Miswiring – Check wire colors to verify I- at AHC is connected to I- at

 

thermostat and I+ is connected to I+.

No RH display, no outdoor

AHC power source – When wired to the Model 8570 thermostat, the AHC

temperature display

must be wired to a continuously ON power source. Use voltmeter to verify

 

presence of 24VAC (nominal) at AHC.

 

 

 

AHC not operating correctly – check red diagnostic light on AHC.

 

 

No RH display, outdoor temperature OK

No valid reading available – run fan for at least 40 seconds.

 

 

RH display, outdoor temperature @ 20°F

AHC set for manual mode of operation. Wire an outdoor sensor to the AHC

 

or wire an outdoor sensor to the thermostat.

 

 

- 25 -

Page 29
Image 29
Aprilaire Model 8570 installation instructions Troubleshooting AHC Connection