TROUBLESHOOTING – HEATING OPERATION

Symptom

Cause

 

 

Thermostat does not call for heat

Minimum-off times. Change the mode to OFF first, then change the mode to

HEAT and make a call for heat.

 

 

 

Heating does not come on at all

RH terminal not connected – see wiring diagrams.

 

Heating equipment power not on.

 

Auxiliary Heat does not come on

High Balance point limit – set balance point higher than outdoor temperature

or disconnect outdoor temperature sensor during system checkout.

 

 

Furnace plenum sensor keeps fan on – normal.

 

 

Fan stays on after heat call

Blower Extension for humidifier operation. Verify that the message

"HUMIDIFYING" appears at the message center, alternating with the time

 

 

and date and any other currently active messages.

Fan comes on before heat starts, or

Change position of ELEC/GAS dip switch – ELEC for electric heat systems

(fan on with heat call) or to GAS for fossil fuel systems where the fan is

Fan does not come on with heat

controlled internally by the heating equipment.

 

 

 

Cooling comes on instead of heat

Reversing valve wiring.

 

Miswiring – check wire colors at thermostat and HVAC equipment.

 

Takes longer than 4 minutes for auxiliary

SINGLE/MULTI dip switch set incorrectly – set to SINGLE for single-stage

heat to come on after compressor heat.

compressor systems.

 

 

- 27 -