Controls Configuration & Adjustments...
5.Defrost Sensor Calibration... continued:
G.Once the correct temperature value has been selected, not pressing any buttons for
6.Spa Dead Band Differential [dBS]:
In the heating mode, the dead band differential determines the number of degrees the water temperature must fall below the set point before the thermostat closes. In the cooling mode, the dead band differential determines the number of degrees the water temperature must rise above the set point before the thermostat closes. When in the
A.Follow the steps 1, A through 1, D to enter the service menu. Once [dEL] is displayed, press the [POOL/SPA] key until the display shows [dBS] (Spa Dead Band Differential).
B.With the service menu parameter [dBS] displayed, pressing either the [UP] or [DOWN] arrow keys, once, will display the current setting. Using the [UP] or [DOWN] arrows keys will increase or decrease the value respectively. The differential is adjustable in 1o increments from 1 to
C.Once the desired dead band value has been selected, not pressing any buttons for
7.Pool Dead Band Differential [dBP]:
In the heating mode, the dead band differential determines the number of degrees the water temperature must fall below the set point before the thermostat closes. In the cooling mode, the dead band differential determines the number of degrees the water temperature must rise above the set point before the thermostat closes. When in the
A.Follow the steps 1, A through 1, D to enter the service menu. Once [dEL] is displayed, press the [POOL/SPA] key until the display shows [dBP] (Pool Dead Band Differential).
B.With the service menu parameter [dBP] displayed, pressing either the [UP] or [DOWN] arrow keys, once, will display the current setting. Using the [UP] or [DOWN] arrows keys will increase or decrease the value respectively. The differential is adjustable in 1o increments from 1 to 5 degrees.
(Continued on Next Page)