Aquacal 120, 155 owner manual Placement of Heater, IndoorInstallation, OutdoorInstallation

Models: 120 155

1 65
Download 65 pages 55.29 Kb
Page 39
Image 39
INSTALLATION

INSTALLATION

Placement of Heater

-Indoor Installation-

Indoor installations can be problematic, and for that reason are discouraged. However, if no viable alternative exists, indoor installations may be successfully accomplished provided very exacting cri- teria is addressed. Every indoor installation is unique; therefore, there are no specific guidelines for this type of installation. If considering an indoor installation, you are strongly urged to contact the AquaCal Engineering department (800-786-7751) for assistance prior to proceeding.

-Outdoor Installation-

Service and Operational Clearances:

To operate correctly, heat pumps require large volumes of air moving over the heat collector. allow adequate clearance between the heat pump and walls, fences, shrubs, or other objects. Refer to required clearance drawings below.

Allow five (5) feet of vertical clearance between the top of the heat pump and any roof overhang or other obstruction. This clearance prevents cold discharge air from recirculating back into the heat pump (recirculation would reduce the overall performance of the heat pump).

The access panel requires removal during installation and service. Do not place plumbing, or other items, closer than 30” from the front of the heater.

Code Required Clearances:

In addition to the previously stated clearance requirements, follow all applicable local, state, and national requirements relative to spacing from other objects or equipment.

Required Installation Clearances

OVERHANG

WITH GUTTER

RAIN RUN-OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUST BE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIRECTED AWAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FROM UNIT.

 

 

 

 

 

 

 

 

 

 

 

5 FT. MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLEARANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30”

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 & 120 MODELS

 

 

CLEARANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1- FT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

155 MODELS 2-FT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(REAR)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIDE VIEW (NO SCALE)

FRONT-REAR-OVERHEAD

100& 120 MODELS 12-INCHES 155 MODELS 24-INCHES

(REAR)

 

 

24-

24-

 

 

INCHES

INCHES

 

 

(SIDE)

(SIDE)

 

 

 

 

 

 

 

 

 

30-INCHES

(FRONT)

TOP VIEW (NO SCALE)

FRONT-SIDES-REAR

39

Page 39
Image 39
Aquacal 120, 155 Placement of Heater, IndoorInstallation, OutdoorInstallation, Required Installation Clearances