Defrost Systems- Described

DEFROST CYCLE (HEAT ONLY UNITS):

The microprocessor controller monitors the heater’s air-coil temperature, minimizing air-coil freeze- up during cooler weather conditions. If the controller senses air-coil temperatures conductive to mak- ing ice, the heater’s compressor operation is interrupted while the fan is allowed to continue in opera- tion.

With the compressor off, the air-coil begins to warm to the surrounding air temperature. When air-coil temperatures rise above approximately 38oF, the compressor is restarted and heating resumes.

In the event air temperatures remain below approximately 38oF, the compressor will remain off until the air temperature rises above 38oF. The unit will not heat the water as long as the compressor remains off.

During defrost cycles, when the controller has stopped compressor operation, the display will read: [FS].

DEFROST CYCLE (HEAT & COOL UNITS):

The microprocessor controller, in conjunction with the defrost sensor, constantly monitors the heater’s evaporator (air-coil) temperature. Should the controller sense ice or frost has formed on the evapora- tor, sufficient in amount as to affect the heater’s performance, an active defrost cycle (more below) is initiated. Before initiating a defrost command, the controller defrost logic looks at both the air-coil temperature, and the length of time the coil has remained at an ice-making temperature.

Active defrost involves using hot refrigerant gas, from the compressor, to rapidly remove ice or frost from the evaporator coil. In practice, during a hot gas defrost cycle, valving, internal within the refriger- ant system, reverses the flow of the refrigerant; this reversal of flow temporarily makes the air-coil the condenser. During hot gas defrost, the air-coil warms very quickly, and accumulated ice and frost is rapidly melted. Under most conditions the evaporator will be completely cleared in under 5-minutes.

HEAT & COOL DEFROST SEQUENCE DETAILS:

When the controller senses air-coil temperatures conductive to making ice, the unit will enter a 50-minute defrost delay (counting) period.

During the counting period, the fan and compressor will continue to operate, and the water will continue to be heated. During the counting period it is normal to see a moderate amount of frost and ice formation on the air coil.

If, after the 50-minute counting period, the controller senses a need to defrost:

1.The refrigerant circuit reversing valve will be activated, changing the flow of hot refrigerant gas from the pool water heat exchanger to the air-coil.

2.Fan operation will be suspended, permitting maximum heating of the air-coil.

3.The reverse cycle will continue until either:

A.The air-coil attains a predetermined temperature (indicative of total defrost), or;

B.Until 5-minutes have elapsed (regardless of total defrost having occurred).

During hot gas defrost cycles, the compressor will not deactivate; rather, the compressor will continue operation throughout the sequence. Upon completion of the defrost cycle (as terminated per “A” or “B,” above), the reversing valve will be deactivated, fan operation will recommence, and water heating will resume.

55

Page 55
Image 55
Aquacal 120, 155 owner manual Defrost Systems- Described

120, 155 specifications

Aquacal 155,120 is a highly regarded pool heater known for its efficiency, reliability, and advanced technology. This product stands out in the competitive market of swimming pool heating solutions, making it a popular choice among pool owners and professionals alike.

One of the main features of the Aquacal 155,120 is its high-performance heat exchanger, made from durable titanium. This material ensures resistance to corrosion and enhances the longevity of the heater. The titanium heat exchanger is designed to facilitate maximum heat transfer, providing rapid warming of pool water and ensuring a consistent swimming experience.

The units are equipped with a powerful compressor that utilizes advanced inverter technology. This technology enables the heater to adjust its output according to the pool’s needs, optimizing energy consumption and reducing operational costs. The inverter-driven compressor allows the Aquacal 155,120 to operate quietly, making it ideal for residential settings where noise could be a concern.

Aquacal has designed the unit to be user-friendly, featuring an intuitive digital control panel. This control panel allows users to easily monitor and adjust the temperature settings, ensuring that the water temperature can be maintained at a comfortable level. Additionally, this feature includes programmable settings to enable automatic heating schedules, providing convenience and energy savings for pool owners.

The Aquacal 155,120 is also known for its energy efficiency. With a high coefficient of performance (COP), this heater can deliver more heat output per unit of energy consumed compared to traditional heating systems. This efficiency contributes to a lower carbon footprint, making it an environmentally friendly choice for heating pool water.

Furthermore, the unit is designed with robust insulation, which minimizes heat loss and maximizes energy retention. This insulation helps maintain the desired water temperature for longer periods, reducing the need for frequent reheating and thereby lowering energy expenses.

In summary, the Aquacal 155,120 is an outstanding choice for pool owners looking for an efficient, reliable, and technologically advanced heating solution. With its titanium heat exchanger, inverter technology, user-friendly control panel, energy efficiency, and excellent insulation, this pool heater stands out as a top contender for modern pool heating needs. Whether for leisure activities or extended swimming seasons, the Aquacal 155,120 ensures a comfortable and enjoyable swimming experience.