Ariston 41-116-05 F Ig, Siting The Appliance, Overall Dimensions, Clearances

Models: 41-116-05

1 20
Download 20 pages 25.86 Kb
Page 5
Image 5
2.2 SITING THE APPLIANCE

2.2 SITING THE APPLIANCE

 

 

mm400

 

 

60 mm

132

132

 

C

E

mm

 

 

300

FIG. 2.1

 

 

The appliance may be installed in any room or indoor area, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the appliance in a room containing a bath or shower.

Where a room-sealed appliance is installed in a room containing a bath or shower the appliance and any electrical switch or appliance control, utilising mains electricity should be situated so that it cannot be touched by a person using the bath or shower.

The location must permit adequate space for servicing and air circulation around the appliance as indicated in paragraph 2.4.

The location must permit the provision of an adequate flue and termination. For unusual locations special procedures may be necessary.

BS 6798-1987 gives detailed guidance on this aspect.

A compartment used to enclose the appliance must be designed specifically for this purpose. No specific ventilation requirements are needed for the installation within a cupboard.

This appliance is not suitable for outdoor installation.

The type C appliances (in which the combustion circuit, air vent intake and combustion chamber are air-tight with respect to the room in which the appliance is installed) can be installed in any type of room.

Secondary ventilation is not required with this boiler. The boiler must be installed on a solid, permanent wall to prevent access from the rear.

2.3OVERALL DIMENSIONS

LEGEND:

A = Central Heating Flow (3/4”)

C = Gas Inlet (3/4”)

E= Central Heating Return (3/4”) mm = Clearances

450 mm

2.4CLEARANCES

In order to allow for access to the interior of the boiler for maintenance purposes, the boiler must be installed in compliance with the minimum clearances indicated in FIG. 2.1

2.5MOUNTING THE APPLIANCE

2.6ELECTRICAL CONNECTION

Fasten the boiler in place using the template and anchors supplied with the unit. It is highly recommended that a spirit level be used to position the boiler so that it is perfectly level.

For additional information, please consult the instructions contained in the connection kit and the flue kit.

For safety purposes, have a competent person carefully check the electrical system in the property, as the manufacturer will not be held liable for damage caused by the failure to earth the appliance properly or by anomalies in the supply of power. Make sure that the residential electrical system is adequate for the maximum power absorbed by the unit, which is indicated on the rating plate. In addition, check that the section of cabling is appropriate for the power absorbed by the boiler.

5

Page 5
Image 5
Ariston 41-116-05 installation instructions F Ig, Siting The Appliance, Overall Dimensions, Clearances