Model 24 RFFI System
MAKE SURE THAT:
1. There is sufficient water in the system
2. The gas is turned on
3. The electrical supply is turned on
PUSH THE ON/OFF
BUTTON TO ON
TABLE
I and II
SUMMER
IS THE
POWER L.E.D. AND
DISPLAY ON?
YES | DOES A STOP CODE |
| APPEAR ON THE DISPLAY? |
POSITION OF THE SUMMER/
WINTER SELECTOR
NO
1. Check the fuses
2.Check the power supply to the control panel
3.Check/replace the ON/OFF button
4.Check the connection between the main and display P.C.B.s
5.Check/replace the
main and display P.C.B.s
WINTER
OFF (green L.E.D. off):
C.H. ONLYcylinder active
SELECTOR
ON/OFF
OFF (green L.E.D. off):
cylinder activeC.H. ONLY
SELECTOR
ON/OFF
ON (green L.E.D. on):
cylinder excluded
The
C.H. flow
temperature
is lower than 80° C YES and the temperature of the
cylinder is at least 5° C below the one selected.
NO
The
C.H. flow
temperature
YES is lower than 80° C and the temperature of the
cylinder is at least 5° C below the one selected.
NO
ON (green L.E.D. on):
cylinder excluded
|
|
| |
ELECTRONIC |
|
| |
|
| ||
Is there a condition for it to be active? |
|
| |
(- flow temp. < 3° C | YES | ||
- outdoor temp. < | |||
|
| ||
- Jumper 4 selects the pump |
|
| |
for continuous |
|
| |
operation) |
|
| |
NO |
|
| |
|
|
| |
THERE IS NO CALL FOR PUMP OPERATION |
|
| |
|
|
|
|
|
| MUST |
| YES |
| THE TIME CLOCK |
|
| AND/OR ROOM THERMOSTAT | |
|
| ||
|
|
| BE ACTIVATED? |
|
|
| NO |
|
|
| |
|
|
| ELECTRONIC |
|
|
| |
|
|
| Is there a condition for it to be active? |
|
| YES | (- flow temp. < 3° C |
|
| - outdoor temp. < | |
|
|
|
-Jumper 4 selects the pump for continuous
operation)
NO
THERE IS NO CALL FOR PUMP OPERATION
A
20