2.8 COLD WATER

The cold water combination valve can be connected either close by

COMBINATION VALVE

the unit or alternatively it may be installed in a remote position from

 

the unit as there is no requirement to site it in close proximity to the

 

cylinder. This allows a flexible and convenient installation. However, it

 

is important to note allowances for the discharge pipe work from the

 

expansion relief valve must be accounted for.

A balancing port is supplied on the 22mm valves (for units above 50 litres) and 28mm valves (for 500 litres units) allowing balanced cold water supply to the rest of the building giving constant results for mixer and shower valves. If the facility is not needed a plug is supplied. Refer to FIG. 2.7 and FIG. 2.8

Although this facility is not built into the 15mm valve (supplied with model ST50), a tee piece may be inserted between the two components giving the same result. Refer to FIG. 2.6

NOTE!

THERE SHOULD BE NO OTHER VALVES FITTED BETWEEN THE CYLINDER AND

THE EXANSION VALVE.

SERVICEABLE 1/2” PRESSURE

REDUCING CARTRIDGE AND

LINE STRAINER

NON-RETURN

EXPANSION RELIEF VALVE (SET AT 6 BAR)

VALVE (WITHIN HOUSING)

15mm

COLD MAINS IN

15mm

TO CYLINDER

TEE PIECE

3/4” B.S.P. CONNECTIONS

FOR BALANCED

FOR EXPANSION VESSEL

COLD WATER

 

TAKE OFF

 

(NOT SUPPLIED)

 

FIG. 2.6

For Model ST 50

www.tradeplumbing.co.uk Call Sales On 08708034288

8

Page 8
Image 8
Ariston Unvented Hot Water Storage Cylinders manual Expansion relief valve must be accounted for