4 - Operations
4.4 PARAMETER SETTING
Operator mode
274.8
P0
1st GROUP
AIs.pAL1 alarm threshold [1]
(see pag. 24)
Values
modification
Parameter Modification/
menùselection
selectionentry
A
The parameter setting procedure
PASS
5000
Password entry [3]
only if Code value ≥5000
(see pages 26…27)
Code entry [3] from 5000 to 9999 Must be equal to the value of the parame-
P0
AL2 alarm threshold [2]
A2s.p(see pag. 24)
P5:0
Proportional band p.b. (PID algorithm only) 0.5…999.9% of span
has a timeout. If no keys are pressed for, at least, 30 seconds, the controller switches back, auto- matically, to the operator mode.
Back to the Operator mode
NO
OK
ter Code
YES
Integral time
t.i. (PID algorithm only) 0ff / 0.0 ...100.0 min.
P1:00
After having selected the parameter or the code, press S and G to display or modify the value (see pag. 20) The value is entered when the next parameter is selected, by pressing the R key.
Pressing the Q key, the next group of parameters is presented on the display.
Note
[1]It is presented only if the controller has been configured with 2 alarms. Digit L of the con- figuration code is assigned to 4 or 5
[2]It is not presented if the controller has been configured with alarm n° 2 not active or of sensor break type. Digit N of the configu- ration code is assigned to 0 or 1.
[3]If password is 0000 to 4999, parameter set- ting will be available to the operator with- out entering this password number. If pass- word is 5000 to 9999, parameter setting will only be available by entering this pass- word number.
Derivative time
t.d. (PID algorithm only)
0ff / 0.01 ... 10.00 min.
P20
Cycle time
t.c. (PID algorithm only) 1 ... 200 sec.
22