6 - Technical specification

 

 

 

 

 

Features

 

Description

 

 

(at 25°C enviromental temp.)

 

 

 

 

 

 

 

 

 

Ramp up and down

0.1…999.9 digit/min (Off = 0)

 

Setpoint

 

Low limit

From low range to the high limit

 

 

 

High limit

From low limit to the high range

 

 

 

 

 

OP4 PV retransmission

 

Galvanic isolation: 500 V~/1 min

Current output: 0/4…20mA 750/15V max

 

Resolution 12bit (0.025%)

(option)

 

 

Accuracy: 0.1 %

 

 

 

 

 

 

One shot Fuzzy-Tuning

 

The controller selects automatically the best

Step response

 

with automatic selection

 

method according to the process conditions

Natural frequency

 

Serial comm. (option)

RS485 isolated, Modbus/Jbus protocol, 1200, 2400, 4800, 9600 bit/sec 2 wires

Auxiliary Supply

+18V– ±20%, 30mA max

for an external transmitter supply

 

Measure input

 

Detection of out of range, short circuit or sensor break with automatic

 

 

activation of the safety strategies and alerts on display

 

 

 

Operational safety

 

 

 

Control output

 

Safety value: 0…+100%. (user enabled/disabled)

 

Parameters

 

parameter and configuration data are stored in a non volatile memory for

 

 

an unlimited time

 

 

 

 

Access protection

 

Password to access the configuration and parameters data

 

 

 

100 - 240V~ (- 15% + 10%) 50/60Hz

 

Power supply

 

or 24V~ (- 25% + 12%) 50/60Hz and 24V– (- 15% + 25%)

 

 

 

Power consumption 1.6W max

 

Electric safety

 

Compliance to EN61010, installation class 2 (2500V) pollution class 2

General

Electromagnetic

 

Compliance to the CE standards for industrial system and equipment

characteristics

compatibility

 

 

 

 

Approvals

 

UL, cUL

 

Protection EN650529

 

IP20 termination unit

 

 

IP65 front panel

 

 

 

 

Dimensions

 

1/32 DIN - 48 x 24, depth 120 mm, weight 100 gr. apx.

31