4 - Operations

4.5PARAMETER

1st GROUP

The controller parameters have been organized in group, according to their functionality area.

#AIs.AL1p alarm threshold

The threshold is presented only if the controller have been configured with 2 alarms. ( Digit L of the configuration code assigned to 4 or 5)

#A2s.AL2p alarm threshold

The alarm occurrences handle the OP1 and OP2 outputs, in different ways, according to the configured types of alarms, as illustrated.

#p.b.Proportionalband

This parameter specifies the proportional band coefficient that multiplies the error (SP - PV)

#t.i.Integraltime

It is the integral time value, that

Sensor break or input disconnection

SensorVisualisation

over-range

T

under-range

Absolute alarm (full scale)

On Active

Off high

On

OffActive

low

hy

 

 

low range

high range

Alarm threshold

 

Deviation alarm

 

 

SP

On

Active

 

Off

high

On

 

Active

Off

 

 

low

hy

 

 

- low range

+ high range

Alarm threshold

 

 

Band alarm

 

 

SP

 

OnActive

 

 

Off out

On

OffActive

in

hyhy

full scale

full scale

alarm threshold

specifies the time required by the integral term to generate an output equivalent to the proportional term. When Off the integral term is not included in the control algorithm.

#t.d.Derivativetime

It is the derivative term coefficient that specifies the time required by the proportional term P to reach the level of D. When Off the derivative term is not included in the control algorithm.

#t.c.Control output cycle time

It’s the cycle time of the time proportioning control output. The PID control output is provided through the pulse width modulation of the digital waveform.

#O.C.Overshootcontrol

This parameter specifies the span of action of the overshoot control. Setting lower values (0.99 —> 0.01) the overshoot generated by a Setpoint change is reduced. The overshoot control doesn’t affect the

24