2nd GROUP

tune

Entry of digits

I-L-M-N of the configuration code

(chapter 3.2 page 16)

pAss Password entry [3] only if Code

value <5000

Code entry [3] 33 from 0 to 4999

(33 default from factory)

The entered password must correspond to the one store in the Code parameter.

YES OK NO

4 - Operations

Note

Pressing the Q the next group of parameters is displayed.

[1]Table of the supported Engineering Units.

Centigrade degrees *

°C

 

 

Fahrenheit degrees *

°f

 

 

none

none

 

 

mV

nU

 

 

Volt

U

 

 

mA

MA

I L MN

2002 Conf

Engineering

units Unit (see table)

N° of decimals

(linear scale only) sc.d.d 0…3

A

If the controller has not been

configured Conf is shown on the front panel at the power up. In this situation, the controller has its outputs and inputs not active. This situation ends when a correct

configuration code is entered.

Ampere

A

 

 

Bar

bAr

 

 

PSI

psI

 

 

Rh

rh

 

 

pH

ph

*For inputs from thermocouple or resistance thermometer, the choice is between °C and °F only.

[2]Range of min 100 digits.

[3]If password is 0000 to 4999, parameter set- ting will be available to the operator with- out entering this password number. If pass- word is 5000 to 9999, parameter setting will only be available by entering this pass- word number.

27