Image 17

Technical

Specifications

Operating Limits

 

 

Ambient Temperature

32° F to 140° F (0° C to 60° C)

Relative Humidity

 

 

Tolerance

20% to 95%, Non-Condensing

Power

85 to 250 V ±10%, 50/60 Hz

Sensor Range

(Single-Phase) 120 to 250 Vdc

 

 

Type J Thermocouple

OTC25 N/L: 6 to 926° F

 

 

(-14 to 496° C)

 

OTC25 P:

32 to 999° F

 

 

(0 to 537° C)

Type K Thermocouple

OTC25 P:

0 to 999° F

Performance

 

(-17 to 537° C)

 

 

Accuracy

±0.3% of Full Scale

 

(±0.10% Typical), ±1 Digit

Setpoint Resolution

1° F/C

 

Repeatability

±1 Count

 

Temperature Stability

5 µV /° C (Maximum)

TC Cold-End Tracking

0.05° C /° C Ambient

Noise Rejection

100 dB Common Mode,

 

70 dB Series Mode

Temperature Sampling

3.7 Hz (270 ms)

Control Characteristics

 

 

Control Hysteresis

2 to 252° F (1 to 140° C)

Display Offset

-126 to 126° F (-70 to 70° C)

Mechanical Characteristics

 

 

Display

7-segment LED,

 

alphanumeric: 3 digits

Display Height

0.56" (14.22 mm)

Color

Orange

 

Front-Panel Cutout

3.622" x 3.622"

 

(92 mm x 92 mm)

Bezel Outside Dimensions

3.780" x 3.780"

 

(96 mm x 96 mm)

Bezel Height

0.250" (6.35 mm)

Case Depth

3.515" (89.28 mm)

Weight

< 15 oz (425 g)

Connections

7

 

Contacts

“Fast-On” .250” (6.35 mm)